-
-
9
5.2
Inverter Setting
Execute the following constant setting, whenever necessary, before starting communications between the
inverter and the PROFIBUS-DP master.
5.2.1 F7, G7 Series
Constant
No.
Name
Description
Factory
setting
b1-01
Reference selection
∗
1
Set the frequency reference input method.
0: Digital Operator
1: Control circuit terminal (analog input)
2: MEMOBUS communications
3: Option Card
4: Pulse train input
1
b1-02
Operation method selection
∗
1
Set the run command input method
0: Digital Operator
1: Control circuit terminal (sequence input)
2: MEMOBUS communcations
3: Option Card
1
F6-01
Stopping method after communications
errors
Set the stopping method for communications errors.
0: Deceleration stop using deceleration time in C1-02.
1: Coast to stop
2: Emergency stop using deceleration time in C1-09
3: Continue operation
∗
2
1
F6-02
Input level of external error from
Communications Option Card
0: Always detect.
1: Detect during operation.
0
F6-03
Stopping method for external error from
Communications Option Card
0: Deceleration stop using deceleration time in C1-02
1: Coast to stop
2: Emergency stop using deceleration time in C1-09
3: Continue operation
∗
2
1
∗
1: To run/stop through the PROFIBUS-DP communications, set "3" to b1-02. To set frequency, set "3" to b1-01.
∗
2: Selecting "Continuous operation" continues the operation with the inverter single-unit at fault occurrence. Therefore,
provide some other measures (emergency stop switch, etc.) to assure safe operation.
AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France
Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr