Digital Operator Display Functions and Levels
5-
5
C6-02
Carrier
Frequency
Selection
Selects the number of pulses per
second of the output voltage
waveform. Setting range determined
by C6-01 setting.
0: Low noise
1: Fc = 2.0 kHz
2: Fc = 5.0 kHz
3: Fc = 8.0 kHz
4: Fc = 10.0 kHz
5: Fc = 12.5 kHz
6: Fc = 15.0 kHz
OF: Program (Determined by the
settings of C6-03 thru C6-05)
0 to F
6
*2
No
Q
Q
Q
Q
-
*12
224H
Carrier
Freq Sel
C6-11
Carrier
Frequency
for
Open-loop
Vector
Control 2
Selects the carrier frequency during
Vector Control 2 wo/PG.
1: 2kHz (3-phase modulation)
2: 4kHz (3-phase modulation)
3: 6kHz (3-phase modulation)
4: 8kHz (3-phase modulation)
1 to 4
4
*2
No
-
*12
-
*12
-
*12
-
*12
Q
22DH
Carrier
Freq Sel
d1-01
Frequency
Reference 1 Setting units are affected by o1-03.
0
to
400.00
*9
0.00Hz
Yes
A
A
A
A
A
280H
Reference 1
d1-02
Frequency
Reference 2
Frequency reference when
multi-function input "Multi-step speed
reference 1" is ON. Setting units are
affected by o1-03.
0.00Hz
Yes
A
A
A
A
A
281H
Reference 2
d1-03
Frequency
Reference 3
Frequency reference when
multi-function input "Multi-step speed
reference 2" is ON. Setting units are
affected by o1-03.
0.00Hz
Yes
A
A
A
A
A
282H
Reference 3
d1-04
Frequency
Reference 4
Frequency reference when
multi-function input "Multi-step speed
reference 1, 2" is ON. Setting units are
affected by o1-03.
0.00Hz
Yes
A
A
A
A
A
283H
Reference 4
d1-17
Jog
Frequency
Reference
Frequency reference when: "Jog
frequency reference" is selected via
multi-function input terminals. "Jog
frequency reference" has priority over
"multi-step speed reference 1 to 4".
Parameter d1-17 is also the reference
for the JOG key on the Digital Opera-
tor, and the multi-function inputs
"forward jog" and "reverse jog".
Setting units are affected by o1-03.
6.00Hz
Yes
Q
Q
Q
Q
Q
292H
Jog
Reference
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
MODBUS
Register
Display
V/f
V/f
with
PG
Open
-loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
Summary of Contents for CIMR-G7U
Page 2: ......
Page 7: ...v...
Page 32: ...1 18...
Page 90: ...3 16...
Page 112: ...4 22...
Page 382: ...6 164...
Page 410: ...7 28...
Page 454: ......