Table 5.5 V/F Pattern for Drive Capacity G7U2055 and higher for 208-240V Class
Parameter
No.
Name
Unit
Factory Setting
E1-03
V/F Pattern
Selection
–
0
1
2
3
4
5
6
7
E1-04
Max. Output
Frequency
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
E1-05
Max. Output
Voltage
V
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
E1-06
Max. Voltage
Frequency
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
E1-07
Mid. Output
Frequency
V
2.5
3.0
3.0
3.0
25.0
25.0 30.0
30.0
E1-08
Mid. Output
Voltage
V
13.8
13.8
13.8
13.8
40.2
57.5
40.2
57.5
E1-09
Min. Output
Frequency
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
E1-10
Min. Output
Voltage
V
6.9
6.9
6.9
6.9
5.7
6.9
5.7
6.9
1.
The setting shown are for 208-240Vac Drives. The values will double for 380-480Vac Drives.
.
2. These default values are for V/F or V/F with PG control methods (A1-02 = 0 or 1)
Table 5.5 V/F Pattern for Drive Capacity G7U2055 and higher for 208-240V Class (continued)
Parameter
No.
Name
Unit
Factory Setting
E1-03
V/F Pattern
Selection
–
8
9
A
B
C
D
E
F & FF
E1-04
Max. Output
Frequency
Hz
50.0
50.0
60.0
60.0
90.0
120.0
180.0
60.0
E1-05
Max. Output
Voltage
V
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
E1-06
Base Frequency
Hz
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
E1-07
Mid. Output
Frequency
V
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
E1-08
Mid. Output
Voltage
V
17.2
23.0
17.2
23.0
13.8
13.8
13.8
13.8
E1-09
Min. Output
Frequency
Hz
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
E1-10
Min. Output
Voltage
V
8.0
10.3
8.0
12.6
6.9
6.9
6.9
6.9
1.
The setting shown are for 208-240Vac Drives. The values will double for 380-480Vac Drives.