10
-18
UL Markings
The G7 is UL listed to UL Standard 508C, UL FILE No.: E13145.
Conformance to UL Standard
To comply with UL standard, follow the appropriate installation instructions.
Installation Site
Install the Inverter in a pollution degree 2 environment or equivalent.
Specification of Closed-Loop Connector
The closed-loop connectors must be installed on conductors before installing to terminal blocks.
Use UL Listed closed-loop connectors shown in
Table 10.5
below.
Table 10.5 JST Closed-Loop Connector Model
Inverter
Model CIMR-G7
JST Kit P/N
Input
Wire Size
Input
JST Kit P/N
Output
Wire Size
Output
JST Kit P/N
2015
2 AWG
38-8
4 AWG
22-8
2018
2 AWG
38-8
2 AWG
38-8
2022
1/0 AWG
60-8
1/0 AWG
60-8
2030
3/0 AWG
80-10
3/0 AWG
80-10
2037
4/0 AWG
100-10
4/0 AWG
100-10
2045
1/0 AWG
60-10 (2 per Ph)
1/0 AWG
60-10 (2 per Ph)
2055
3/0 AWG
80-10 (2 per Ph)
3/0 AWG
80-10 (2 per Ph)
2075
250 kcmil
150-12 (2 per Ph)
4/0 AWG
100-12 (2 per Ph)
2090
400 kcmil
200-12 (2 per Ph)
250 kcmil
150-12 (2 per Ph)
2110
400 kcmil
200-12 (2 per Ph)
300 kcmil
150-12 (2 per Ph)
4018
6 AWG
14-6
6 AWG
14-6
4022
4 AWG
22-6
4 AWG
22-6
4030
2 AWG
38-8
4 AWG
22-8
4037
2 AWG
38-8
2 AWG
38-8
4045
1/0 AWG
60-8
1/0 AWG
60-8
4055
3/0 AWG
80-10
3/0 AWG
80-10
4075
4/0 AWG
100-10
4/0 AWG
100-10
4090
1/0 AWG
60-10 (2 per Ph)
1/0 AWG
60-10 (2 per Ph)
4110
3/0 AWG
80-10 (2 per Ph)
3/0 AWG
80-10 (2 per Ph)
4132
3/0 AWG
80-12 (2 per Ph)
3/0 AWG
80-12 (2 per Ph)
4160
4/0 AWG
100-12 (2 per Ph)
4/0 AWG
100-12 (2 per Ph)
4185
250 kcmil
150-16 (2 per Ph)
250 kcmil
150-16 (2 per Ph)
4220
400 kcmil
200-16 (2 per Ph)
300 kcmil
150-16 (2 per Ph)
4300
650 kcmil
325-16 (2 per Ph)
650 kcmil
325-16 (2 per Ph)