B.2 Parameter Tables
YASKAWA ELECTRIC
TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
153
Pa
ra
me
te
r L
is
t
B
H4-06
(422H)
Terminal AM
Monitor Bias
Terminal AM Bias
Sets the signal level at terminal AM that is equal to 0% of the
selected monitor value.
Default: 0.0%
Min.: -999.9%
Max.: 999.9%
H4-07
(423H)
Terminal FM Signal
Level Selection
Level Select1
0: 0-10 VDC
1: -10 +10 VDC
Sets the signal level at terminal FM.
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min.: 0
Max.: 1
H4-08
(424H)
Terminal AM Signal
Level Selection
AO Level Select2
0: 0-10 VDC
1: -10 +10 VDC
Sets the signal level at terminal AM.
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min.: 0
Max.: 1
H5: MEMOBUS/Modbus Serial Communication
Note:
Restart the drive to enable MEMOBUS/Modbus communication settings.
H5-01
(0425)
Drive Slave Address Serial Comm Adr
Selects drive station node number (address) for MEMOBUS/
Modbus terminals R+, R-, S+, S-. Cycle power for the setting
to take effect.
Default: 1F (Hex)
Min.: 0
Max.: FF
H5-02
(0426)
Communication
Speed Selection
Serial Baud Rate
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19.2 kbps
5: 38.4 kbps
6: 57.6 kbps
7: 76.8 kbps
8: 115.2 kbps
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Cycle power for the setting to take effect.
Default: 3
Range: 0 to 8
H5-03
(0427)
Communication
Parity Selection
Serial Com Sel
0: No Parity
1: Even Parity
2: Odd Parity
0: No parity
1: Even parity
2: Odd parity
Cycle power for the setting to take effect.
Default: 0
Range: 0 to 2
H5-04
(0428)
Stopping Method
after
Communication
Error
Serial Fault Sel
0: Ramp to Stop
1: Coast to Stop
3: Alarm Only
0: Ramp to stop
1: Coast to stop
3: Alarm only
Default: 3
Range: 1, 3
H5-05
(0429)
Communication
Fault Detection
Selection
Serial Flt Dtct
0: Disabled
1: Enabled
0: Disabled
1: Enabled. If communication is lost for more than two seconds, a
CE fault will occur.
Default: 1
Range: 0, 1
H5-06
(042A)
Drive Transmit Wait
Time
Transmit WaitTIM
Set the wait time between receiving and sending data.
Default: 5 ms
Min.: 5
Max.: 65
H5-07
(042B)
RTS Control
Selection
RTS Control Sel
0: Disabled
1: Enabled
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.
Default: 1
Range: 0, 1
H5-09
(0435)
Communications
Fault Detection
Time
CE Detect Time
Sets the time required to detect a communications error.
Adjustment may be needed when networking several drives.
Default: 2.0 s
Min.: 0.0
Max.: 10.0
H5-11
(043C)
Communications
ENTER Function
Selection
Enter CommandSel
0: Enter Required
1: No EnterRequired
0: Drive requires an Enter command before accepting any
changes to parameter settings.
1: Parameter changes are activated immediately without the
Enter command (same as V7).
Default: 1
Range: 0, 1
No.
(Address
Hex)
Name
LCD Display
Description
Values