C.4 MEMOBUS/Modbus Setup Parameters
168
YASKAWA ELECTRIC
TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
■
H5-05: Communication Fault Detection Selection
Enables or disables the CE detection for communications.
Setting 0: Disabled
No communication error detection. The regenerative unit continues operation.
Setting 1: Enabled
If the regenerative unit does not receive data from the master for longer than the time set to H5-09, then a CE fault will be
triggered and the regenerative unit will operate as determined by parameter H5-04.
■
H5-06: Drive Transmit Wait Time
Sets the time the regenerative unit waits after receiving data from a master until responding data.
Figure C.4
Figure C.4 Regenerative Unit Transmit Wait Time Setting
■
H5-07: RTS Control Selection
Enables or disables RTS control.
Setting 0: Disabled. RTS is always on.
Use this setting with point-to-point or multi-drop RS-422 communications.
Setting 1: Enabled. RTS switches while sending.
Use this setting when using RS-485 signals for communications or when using the RS-422 signals for point-to-point
communications.
■
H5-09: Communications Fault Detection Time
Sets the time the communications must be lost before the regenerative unit triggers a CE fault.
■
H5-11: Communications Enter Function Selection
Selects whether an Enter command is necessary to change parameter values via MEMOBUS/Modbus communications.
Refer to
.
Setting 0: Enter command necessary
Parameter changes become effective after an Enter command. An Enter command must only be sent after the last
parameter change, not for each single parameter.
Setting 1: Enter command not necessary
Parameter value changes become effective immediately without the need to send an Enter command.
No.
Name
Setting Range
Default
H5-05
Communication Fault Detection Selection
0 or 1
1
No.
Name
Setting Range
Default
H5-06
Drive Transmit Wait Time
5 to 65 ms
5 ms
No.
Name
Setting Range
Default
H5-07
RTS Control Selection
0 or 1
1
No.
Name
Setting Range
Default
H5-09
Communications Fault Detection Time
0.0 to 10.0 s
2.0 s
No.
Name
Setting Range
Default
H5-11
Communications Enter Function Selection
0 or 1
1
Command message
Response message
Command message
PLC
→
Regenerative Unit
PLC
→
Regenerative Unit
Regenerative Unit
→
PLC
Time
24 bit length H5-06 setting
24 bit length
≥
5 ms
D1000
TOEP_C710656_10B_1_0.book 168 ページ 2015年1月8日 木曜日 午後8時55分