5.7 Diagnosing and Resetting Faults
YASKAWA ELECTRIC
TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
103
Tr
oub
le
sho
o
ti
n
g
5
5.7 Diagnosing and Resetting Faults
When a fault occurs and the regenerative unit stops, follow the instructions below to remove whatever conditions
triggered the fault, then restart the regenerative unit.
◆
Fault Reset Methods
When a fault occurs, the cause of the fault must be removed and the regenerative unit must be restarted. The table below
lists the different ways to restart the regenerative unit.
Note:
If the Run command is present, the regenerative unit will disregard any attempts to reset the fault. Remove the Run command
before attempting to clear a fault situation.
After the Fault Occurs
Procedure
Fix the cause of the fault, restart the
regenerative unit, and reset the fault
Press
on the digital operator when the
error code is displayed.
Resetting via Fault Reset Digital
Input S4
Close then open the fault signal digital input via
terminal S4. S4 is set for “Fault Reset” as
default (H1-04 = 14).
Turn off the main power supply if the above methods do not reset the fault. Reapply
power after the digital operator display has turned off.
LO
RE
ESC
RUN
STOP
ENTER
RESET
ALM
DIGITAL OPERATOR JVOP-182
REV
DRV
FOUT
YEC
S4
Regenerative Unit
Fault Reset Switch
SC
YEC
ON
OFF
TOEP_C710656_10B_1_0.book 103 ページ 2015年1月8日 木曜日 午後8時55分