B.2 Parameter Tables
YASKAWA ELECTRIC
TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
149
Pa
ra
me
te
r L
is
t
B
◆
H: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
No.
(Address
Hex)
Name
LCD Display
Description
Values
H1: Multi-Function Digital Inputs
H1-01
(438H)
Multi-Function
Digital Input
Terminal S1
Function Selection
Term S1 Func Sel
Assigns a function to the multi-function digital inputs S1
to S8.
Note:
Set unused terminals to F.
Default: 3C
Min.: 1
Max.: 67
H1-02
(439H)
Multi-Function
Digital Input
Terminal S2
Function Selection
Term S2 Func Sel
Default: 3D
Min.: 1
Max.: 67
H1-03
(400H)
Multi-Function
Digital Input
Terminal S3
Function Selection
Term S3 Func Sel
Default: 24H
Min.: 0
Max.: 67
H1-04
(401H)
Multi-Function
Digital Input
Terminal S4
Function Selection
Term S4 Func Sel
Default: 14H
Min.: 0
Max.: 67
H1-05
(402H)
Multi-Function
Digital Input
Terminal S5
Function Selection
Term S5 Func Sel
Default: F
Min.: 0
Max.: 67
H1-06
(403H)
Multi-Function
Digital Input
Terminal S6
Function Selection
Term S6 Func Sel
Default: F
Min.: 0
Max.: 67
H1-07
(404H)
Multi-Function
Digital Input
Terminal S7
Function Selection
Term S7 Func Sel
Default: F
Min.: 0
Max.: 67
H1-08
(405H)
Multi-Function
Digital Input
Terminal S8
Function Selection
Term S8 Func Sel
Default: 8H
Min.: 0
Max.: 67
H1 Multi-Function Digital Input Selections
H1-
Setting
Function
LCD Display
Description
1
LOCAL/REMOTE selection
Local/Remote Sel
Open: REMOTE (parameter settings determine the source of the frequency
Reference 1 or 2 (b1-01, b1-02 or b1-15, b1-16)
Closed: LOCAL, Frequency reference and Run command are input from
the digital operator
8
Baseblock command (N.O.)
Ext BaseBlk N.O.
Closed: No output
9
Baseblock command (N.C.)
Ext BaseBlk N.C.
Open: No output
C
Analog terminal input selection Term A2 Enable
Open: Function assigned by H3-14 is disabled.
Closed: Function assigned by H3-14 is enabled.
F
Through mode
Term Not Used
Select this setting when using the terminal in a pass-through mode.
14
Fault reset
Fault Reset
Closed: Resets faults if the cause is cleared and the Run command is
removed.
18
Timer function input
Timer function
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in
conjunction with the timer function output (H2-
= 12).
1B
Program lockout
Program Lockout
Open: Parameters cannot be edited (except for U1-01 if the reference
source is assigned to the digital operator).
Closed: Parameters can be edited and saved.