Table i.16 Types of Auto-Tuning for Induction Motors
Type
Setting
Application Conditions and Benefits
Control
Mode
V/f
Stationary Auto-Tuning for Line-
to-Line Resistance
T1-01 = 2
• The drive is used in V/f Control and other Auto-Tuning selections are not
possible.
• Drive and motor capacities differ.
• Tunes the drive after the cable between the drive and motor has been replaced
with a cable over 50 m long. Assumes Auto-Tuning has already been
performed.
• Should not be used for any vector control modes unless the motor cable has
changed.
YES
Rotational Auto-Tuning for V/f
Control
T1-01 = 3
• Recommended for applications using Speed Estimation Speed Search or using
the Energy Saving function in
V/f Control.
• Assumes motor can rotate while Auto-Tuning is executed. Increases accuracy
for certain functions like torque compensation, slip compensation, Energy
Saving, and Speed Search.
YES
Table i.17
lists the data that must be entered for Auto-Tuning. Make sure this data is available before starting Auto-Tuning.
The necessary information is usually listed on the motor nameplate or in the motor test report provided by the motor
manufacturer.
Table i.17 Auto-Tuning Input Data
Input Value
Input Parameter
Unit
Tuning Type (T1-01)
2
Line-to-Line Resistance
3
Rotational for V/f
Control
Motor rated power
T1-02
kW
YES
YES
Motor rated voltage
T1-03
Vac
–
YES
Motor rated current
T1-04
A
YES
YES
Motor rated frequency
T1-05
Hz
–
YES
Number of motor poles
T1-06
-
–
YES
Motor rated Speed
T1-07
r/min
–
YES
Motor iron loss
T1-11
W
–
YES
Table i.18 Types of Auto-Tuning for Permanent Magnet Motors
Type
Setting
Application Conditions and Benefits
Control Mode
OLV/PM
PM Motor Parameter
Settings
T2-01 = 0
• Motor does not rotate during Auto-Tuning.
• Motor test report or motor data similar to
Table i.19
are available.
YES
Table i.19
lists the data that must be entered for Auto-Tuning. Make sure the data is available before starting Auto-Tuning.
The necessary information is usually listed on the motor nameplate or in the motor test report provided by the motor
manufacturer.
Table i.19 Auto-Tuning Input Data
Input Value
Input Parameter
Unit
Tuning Type (T2-01)
0
Motor Parameter
Settings
Control Mode
A1-02
–
5
Motor Type
T2-03
–
–
Motor Rated Power
T2-04
kW
YES
Motor Rated Voltage
T2-05
Vac
YES
Motor Rated Current
T2-06
A
YES
Motor Rated Frequency
T2-07
Hz
YES
Number of Motor Poles
T2-08
–
YES
Stator Single-phase Resistance
T2-10
Ω
YES
i.6 Start Up