3 Startup Procedure and Test Run
122
YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
Note:
•
Energize the drive with factory defaults to show the Initial Setup screen. Push
(Home) to show the HOME screen.
–
Select [No] from the [Show Initial Setup Screen] setting to not display the Initial Setup screen.
•
Push
from the Home screen to show drive monitors.
•
Push
to set
d1-01 [Reference 1]
when the Home screen shows
U1-01 [Frequency Reference]
in LOCAL Mode.
•
The keypad will show [Rdy] when the drive is in Drive Mode. The drive is prepared to accept a Run command.
Table 3.3 Drive Mode Screens and Functions
Mode
Keypad Screen
Function
Drive Mode
Monitors
Sets monitor items to display.
Programming
Mode
Parameters
Changes parameter settings.
User Custom Parameters
Shows the User Parameters.
Parameter Backup/Restore
Saves parameters to the keypad as backup.
Modified Parameters/Fault Log
Shows modified parameters and fault history.
Auto-Tuning
Auto-Tunes the drive.
Initial Setup Screen
Changes initial settings.
Diagnostic Tools
Sets data logs and backlight.
◆
LED Status Ring
The LED Status Ring on the drive cover shows the drive operating status.
A - ALM/ERR
B - Ready
C - RUN
LED
Status
Description
A
ALM/ERR
Illuminated
The drive detects a fault.
The drive detects:
•
Alarm
•
An oPE parameter setting error
•
A fault or error during Auto-Tuning.
Note:
The LED will illuminate to identify a fault if the drive detects a fault and an alarm at the
same time.
OFF
No fault or alarm occurs on the drive.
B
Ready
Illuminated
The drive is operating or is prepared for operation.
The drive is in
STo [Safe Torque OFF]
Mode.
Flashing Quickly
The voltage of the main circuit power supply dropped, and only the external 24 V power
supply provides the power to the drive.
OFF
•
The drive detects a fault.
•
There is no fault and the drive received a Run command, but the drive cannot operate (such
as when in Programming Mode, or when