YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
261
Model
Terminals
Recommen
ded Gauge
AWG, kcmil
Applicable
Gauge
(IP20
Applicable
Gauge
)
AWG, kcmil
Wire
Stripping
mm
Terminal Screw
Tightening
Torque
N
∙
m (lb
∙
in.)
Terminal
Screw
Size
Shape
2047
R/L1, S/L2, T/L3
3
14 - 3
(8 - 3)
18
M5
Slot (-)
2.3 - 2.5
(19.8 - 22)
U/T1, V/T2, W/T3
4
14 - 4
(10 - 4)
18
M5
Slot (-)
2.3 - 2.5
(19.8 - 22)
-, +1, +2
1
14 - 1
(8 - 1)
20
M6
Hex socket cap
(WAF: 5 mm)
5 - 5.5
(45 - 49)
B1, B2
8
14 - 8
(14 - 8)
10
M4
Slot (-)
1.5 - 1.7
(13.5 - 15)
6
8 - 6
(-)
-
M6
Phillips/slot
combo
5.4 - 6.0
(47.8 - 53.1)
2060
R/L1, S/L2, T/L3
1
14 - 1
(6 - 1)
20
M6
Hex socket cap
(WAF: 5 mm)
5 - 5.5
(45 - 49)
U/T1, V/T2, W/T3
3
14 - 3
(6 - 3)
20
M6
Hex socket cap
(WAF: 5 mm)
5 - 5.5
(45 - 49)
-, +1, +2
1/0
14 - 1/0
(4 - 1/0)
20
M6
Hex socket cap
(WAF: 5 mm)
5 - 5.5
(45 - 49)
B1, B2
8
14 - 8
(14 - 8)
10
M4
Slot (-)
1.5 - 1.7
(13.5 - 15)
6
6 - 4
(-)
-
M6
Phillips/slot
combo
5.4 - 6.0
(47.8 - 53.1)
2075
R/L1, S/L2, T/L3
1/0
14 - 1/0
(6 - 1/0)
20
M6
Hex socket cap
(WAF: 5 mm)
5 - 5.5
(45 - 49)
U/T1, V/T2, W/T3
2
14 - 2
(6 - 2)
20
M6
Hex socket cap
(WAF: 5 mm)
5 - 5.5
(45 - 49)
-, +1, +2
2/0
14 - 2/0
(4 - 2/0)
20
M6
Hex socket cap
(WAF: 5 mm)
5 - 5.5
(45 - 49)
B1, B2
6
14 - 6
(14 - 6)
10
M4
Slot (-)
1.5 - 1.7
(13.5 - 15)
6
6 - 4
(-)
-
M6
Phillips/slot
combo
5.4 - 6.0
(47.8 - 53.1)
2088
R/L1, S/L2, T/L3
1/0
6 - 1/0
(6 - 1/0)
27
M6
Hex socket cap
(WAF: 5 mm)
8 - 9
(71 - 80)
U/T1, V/T2, W/T3
1/0
6 - 1/0
(6 - 1/0)
27
M6
Hex socket cap
(WAF: 5 mm)
8 - 9
(71 - 80)
-, +1
2/0
2 - 2/0
(2 - 2/0)
27
M8
Hex socket cap
(WAF: 6 mm)
10 - 12
(89 - 107)
B1, B2
4
14 - 4
(10 - 4)
21
M6
Minus (-)
3 - 3.5
(27 - 31)
6
6 - 4
(-)
-
M6
Hex bolt (cross-
slotted)
5.4 - 6.0
(47.8 - 53.1)