300
YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
Register No.
(Hex.)
Description
0022
Fault Contents
bit 0
1: During data writing, during motor switching
bit 1
Reserved
bit 2
bit 3
1: Upper/Lower Limit Fault
bit 4
1: Data Integrity Fault
bit 5
1: During EEPROM writing
bit 6
0: EEPROM writing
1: Change data only on the RAM
Note:
Enabled when
H5-17 = 1 [ENTER command response @CPU BUSY = Write to RAM Only]
.
bit 7 - F
Reserved
0023
U1-01 [Frequency Reference]
Note:
The unit changes depending on the setting of
o1-03 [Frequency Display Unit Selection]
.
0024
U1-02 [Output Frequency]
Note:
The unit changes depending on the setting of
o1-03 [Frequency Display Unit Selection]
.
0025
U1-06 [Output Voltage Ref] (units: 0.1 V)
Note:
Able to replace the setting unit with
H5-10 [Modbus Register 0025H Unit Sel]
.
0026
U1-03 [Output Current] (units: 0.1 A)
0027
U1-08 [Output Power]
0028
U1-09 [Torque Reference]
0029
Fault Description 2
bit 0
Reserved
bit 1
GF [Ground Fault]
bit 2
PF [Input Phase Loss]
bit 3
LF [Output Phase Loss]
bit 4
rH [Braking Resistor Overheat]
bit 5
Reserved
bit 6
oH4 [Motor Overheat Fault (PTC Input)]
bit 7 - F
Reserved