Model
4002 4003 4005 4006 4007 4009 4015 4018 4024 4031 4039 4045 4060 4075 4091
Out
put
Rated Output
Capacity
(kVA)
1.2
2.2
3.2
3.6
4.7
6.1
10
12
16
20
26
30
39
49
60
Rated Output
Current (A)
1.8
3.4
4.8
5.5
7.2
9.2
14.8
18
24
31
39
45
60
75
91
Overload
Tolerance
150% of the rated output current for 60 s
Note:
Derating may be necessary for applications that start and stop frequently.
Carrier
Frequency
Usable up to 8 kHz without derating.
Derating the output current enables use up to 15 kHz.
Maximum
Output
Voltage (V)
Three-phase 380 V to 480 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum
Output
Frequency
•
AOLV (Advanced Open Loop Vector): 120 Hz
•
CL-V/f (Closed Loop V/f Control), CLV (Closed Loop Vector): 400 Hz
•
V/f (V/f Control), OLV (Open Loop Vector): 590 Hz
Meas
ures
for
Har
mon
ics
DC Reactor
External options
Standard internal
characteristics
Brak
ing
De
vice
Braking
Transistor
Standard internal characteristics
EMC
Filter
EMC Filter
IEC61800-3,
C2/C3
Factory option
•
Models 4xxxB: A category C3 EMC filter is built into the device.
•
Models 4xxxC: A category C2 EMC filter is built into the device.
Power
Sup
ply
Rated
Voltage/Rated
Frequency
•
Three-phase AC power supply 380 V to 480 V at 50/60 Hz
•
DC power supply 513 V to 679 V
Allowable
Voltage
Fluctuation
-15% to +10%
Allowable
Frequency
Fluctuation
±5%
Input Power
(kVA)
1.5
2.8
3.7
5.3
7.1
9.3
13
17
24
33
40
34
46
57
69
*1
The maximum applicable motor output complies with 380 V motor ratings as specified in Annex G of IEC 60947-4-1. The rated
output current of the drive output amps should be equal to or greater than the motor rated current.
*2
Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor,
wiring connections, and power supply impedance.
*3
The rated output capacity is calculated with a rated output voltage of 380 V.
*4
The power supply capacity is calculated with the voltage between lines at 480 V.
Table 9.4 Rating (400 V Class)
Model
4112
4150
4180
4216
4260
4304
4371
Maximum Applicable Motor Output
(kW)
55
75
90
110
132
160
200
Input
Rated Input
Current
(A)
AC
105
142
170
207
248
300
373
DC
129
174
209
254
304
367
457