YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
439
◆
d: Reference Settings
■
d1: Frequency Reference
No.
(Hex.)
Name
Description
Default
(Range)
d1-01
(0280)
RUN
Reference 1
Sets the frequency reference in the units from
o1-03 [Frequency Display
Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
d1-02
(0281)
RUN
Reference 2
Sets the frequency reference in the units from
o1-03 [Frequency Display
Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
d1-03
(0282)
RUN
Reference 3
Sets the frequency reference in the units from
o1-03 [Frequency Display
Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
d1-04
(0283)
RUN
Reference 4
Sets the frequency reference in the units from
o1-03 [Frequency Display
Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
d1-05
(0284)
RUN
Reference 5
Sets the frequency reference in the units from
o1-03 [Frequency Display
Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
d1-06
(0285)
RUN
Reference 6
Sets the frequency reference in the units from
o1-03 [Frequency Display
Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
d1-07
(0286)
RUN
Reference 7
Sets the frequency reference in the units from
o1-03 [Frequency Display
Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
d1-08
(0287)
RUN
Reference 8
Sets the frequency reference in the units from
o1-03 [Frequency Display
Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
d1-17
(0292)
RUN
Jog Reference
Sets the Jog frequency reference in the units from
o1-03 [Frequency
Display Unit Selection]
. Set
H1-xx = 6 [MFDI Function Select = Jog
Reference Selection]
to use the Jog frequency reference.
6.00 Hz
(0.00 - 590.00 Hz)
■
d2: Reference Limits
No.
(Hex.)
Name
Description
Default
(Range)
d2-01
(0289)
Frequency Reference
Upper Limit
Sets maximum limit for all frequency references. This value is a percentage
of
E1-04 [Maximum Output Frequency]
.
100.0%
(0.0 - 110.0%)
d2-02
(028A)
Frequency Reference
Lower Limit
Sets minimum limit for all frequency references. This value is a percentage
of
E1-04 [Maximum Output Frequency]
.
0.0%
(0.0 - 110.0%)
d2-03
(0293)
Analog Frequency
Ref Lower Limit
Sets the lower limit of the master frequency reference (Multi-Step Speed 1)
as a percentage of
E1-04 [Maximum Output Frequency]
.
0.0%
(0.0 - 110.0%)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV