442
YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
E1-13
(030C)
Expert
Base Voltage
Sets the base voltage for the V/f pattern.
0.0 V
(200 V Class: 0.0 -
255.0 V, 400 V Class:
0.0 - 510.0 V)
E1-14
(034C)
Middle Out Freq Volt
Select 1
Sets the mid point A voltage for reverse run used when
b1-23 = 1 [Selection
REV Parameters = Enabled]
.
Determined by A1-02
and E1-03
(200 V Class: 0.0 -
255.0 V, 400 V Class:
0.0 - 510.0 V)
E1-15
(034D)
Minimum Out Freq
Volt Select 1
Sets the minimum output voltage for reverse run used when
b1-23 = 1
[Selection REV Parameters = Enabled]
.
Determined by A1-02
and E1-03
(200 V Class: 0.0 -
255.0 V, 400 V Class:
0.0 - 510.0 V)
E1-16
(034E)
Middle Out Freq Volt
Select 2
Sets the mid point A voltage used when
H1-xx = 38 [MFDI Function
Selection = Counterweight Selection]
.
Determined by A1-02
and E1-03
(200 V Class: 0.0 -
255.0 V, 400 V Class:
0.0 - 510.0 V)
E1-17
(034F)
Minimum Out Freq
Volt Select 2
Sets the minimum output voltage used when
H1-xx = 38 [MFDI Function
Selection = Counterweight Selection]
is ON.
Determined by A1-02
and E1-03
(200 V Class: 0.0 -
255.0 V, 400 V Class:
0.0 - 510.0 V)
E1-18
(0354)
Middle Out Freq Volt
Select 3
Sets the mid point A voltage for reverse run used when
b1-23 = 1 [Selection
REV Parameters = Enabled]
and
H1-xx = 38 [MFDI Function Selection =
Counterweight Selection]
is ON.
Determined by A1-02
and E1-03
(200 V Class: 0.0 -
255.0 V, 400 V Class:
0.0 - 510.0 V)
E1-19
(0355)
Minimum Out Freq
Volt Select 3
Sets the minimum output voltage for reverse run used when
b1-23 = 1
[Selection REV Parameters = Enabled]
and
H1-xx = 38 [MFDI Function
Selection = Counterweight Selection]
is ON.
Determined by A1-02
and E1-03
(200 V Class: 0.0 -
255.0 V, 400 V Class:
0.0 - 510.0 V)
E1-20
(0BF3)
UL Motor1 Sel
Sets the motor characteristics.
0 : Constant Torque
1 : Variable Torque
2 : Auto Distinction
2
(0 - 2)
■
E2: Motor Parameters
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
E2-01
(030E)
Motor Rated
Current (FLA)
Sets the motor rated current in amperes.
Determined by o2-
04
(10% to 200% of
the drive rated
current)
E2-02
(030F)
Motor Rated Slip
Sets the amount of motor rated slip.
Determined by o2-
04
(0.000 - 20.000
Hz)
E2-03
(0310)
Motor No-Load
Current
Set the no-load current for the motor in amperes when operating at
the rated frequency and the no-load voltage.
Determined by o2-
04
(0 to E2-01)
E2-04
(0311)
Motor Pole Count
Sets the number of motor poles.
4
(2 - 120)
E2-05
(0312)
Motor Line-to-Line
Resistance
Sets the line-to-line resistance for motor stator windings.
Determined by o2-
04
(0.000 - 65.000 Ω)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV