452
YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F6-16
(0B8A)
Gateway Mode
Sets the operation mode of the gateway mode and the number of
connected slave drives.
0 : Disabled
1 : Enabled: 1 Slave Drive
2 : Enabled: 2 Slave Drives
3 : Enabled: 3 Slave Drives
4 : Enabled: 4 Slave Drives
0
(0 - 4)
F6-20
(036B)
MECHATROLINK
Station Address
Sets the station address for MECHATROLINK communication. The
drive is necessary to restart when the setting is changed.
0021h
(MECHATRO
LINK-II
:
0020h -
003Fh
,
MECHATRO
LINK-III
:
0003h -
00EFh)
F6-21
(036C)
MECHATROLINK
Frame Size
Sets the frame size for MECHATROLINK communication. Restart
the drive after you change this setting.
0 : 32byte (M-2) / 64byte (M-3)
1 : 17byte (M-2) / 32byte (M-3)
0
(0, 1)
F6-22
(036D)
MECHATROLINK
Link Speed
Sets the communications speed for MECHATROLINK-II. Restart
the drive after you change this setting.
0 : 10 Mbps
1 : 4 Mbps
0
(0, 1)
F6-23
(036E)
MECHATROLINK
Monitor Select (E) Sets the MEMOBUS register used for the monitor functions of
INV_CTL (drive operation control command) and INV_I/O (drive I/
O control command). Restart the drive after you change this setting.
0000h
(0000h - FFFFh)
F6-24
(036F)
MECHATROLINK
Monitor Select (F)
Sets the MEMOBUS register used for the monitor functions of
INV_CTL (drive operation control command) and INV_I/O (drive I/
O control command). Restart the drive after you change this setting.
0000h
(0000h - FFFFh)
F6-25
(03C9)
MECHATROLINK
Watchdog Error
Sel
Sets the motor operation when
E5 [MECHATROLINK Watchdog
Timer Err]
is detected.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
1
(0 - 3)
F6-26
(03CA)
MECHATROLINK
Allowable No of
Err
Sets the number of times that the option must detect a
bUS
alarm to
cause a
bUS [Option Communication Error]
.
2 times
(2 - 10 times)
F6-30
(03CB)
PROFIBUS-DP
Node Address
Sets the node address for PROFIBUS-DP communication. Restart
the drive after changing this setting.
0
(0 - 125)
F6-31
(03CC)
PROFIBUS-DP
Clear Mode
Selection
Sets what the drive will do after it receives the Clear Mode
command.
0 : Reset
1 : Hold Previous State
0
(0, 1)
F6-32
(03CD)
PROFIBUS-DP
Data Format Select Sets the data format of PROFIBUS-DP communication. Restart the
drive after changing this setting.
0 : PPO Type
1 : Conventional
2 : PPO (bit0)
3 : PPO (Enter)
4 : Conventional (Enter)
5 : PPO (bit0, Enter)
0
(0 - 5)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV