458
YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
H1-29
(0B78)
Terminal S9 Function
Select 2
Sets the second function for MFDI terminal S9.
F
(0 - 1FF)
H1-30
(0B79)
Terminal S10
Function Select 2
Sets the second function for MFDI terminal S10.
F
(0 - 1FF)
H1-40
(0B54)
Mbus Reg 15C0h
bit0 Input Func
Sets the MFDI function for
bit 0
of the MEMOBUS/Modbus register
15C0
(Hex.)
.
F
(0 - 1FF)
H1-41
(0B55)
Mbus Reg 15C0h
bit1 Input Func
Sets the MFDI function for
bit 1
of the MEMOBUS/Modbus register
15C0
(Hex.)
.
F
(0 - 1FF)
H1-42
(0B56)
Mbus Reg 15C0h
bit2 Input Func
Sets the MFDI function for
bit 2
of the MEMOBUS/Modbus register
15C0
(Hex.)
.
F
(0 - 1FF)
H1-xx: MFDI Function Selections
Setting
Function
Description
Ref.
0
Brake Release
Check
Create a sequence that turns on the brake release check whenever the brake release
command turns on.
ON : The brake is released.
OFF : The brake is tightened.
2
External Reference
1/2 Selection
Sets the drive to use Run command source 1/2 or Reference command source 1/2 when
in REMOTE Mode.
ON :
b1-15 = [Frequency Reference Selection 2], b1-16 [Run Command Selection 2]
OFF :
b1-01 = [Frequency Reference Selection 1], b1-02 [Run Command Selection 1]
3
Multi-Step Speed
Reference 1
Uses speed references
d1-01 to d1-08 [Multi-Step Speed Reference]
to set a multi-step
speed reference.
4
Multi-Step Speed
Reference 2
Uses speed references
d1-01 to d1-08 [Multi-Step Speed Reference]
to set a multi-step
speed reference.
5
Multi-Step Speed
Reference 3
Uses speed references
d1-01 to d1-08 [Multi-Step Speed Reference]
to set a multi-step
speed reference.
6
Jog Reference
Selection
Enables the JOG Frequency Reference (JOG command) set in
d1-17
. The JOG
Frequency Reference (JOG command) overrides
References 1 to 8 [d1-01 to d1-08]
.
7
Accel/Decel Time
Selection 1
Sets the drive to use
Acceleration/Deceleration Time 1 [C1-01, C1-02]
or
Acceleration/
Deceleration Time 2 [C1-03, C1-04]
.
8
Baseblock
Command (N.O.)
If a baseblock command (N.O.) is input, the drive output will stop and the motor will
coast to stop.
ON : Baseblock (drive output stop)
OFF : Normal operation
9
Baseblock
Command (N.C.)
If a baseblock command (N.C.) is input (turned OFF), the drive output will stop and the
motor will coast to stop.
ON : Normal operation
OFF : Baseblock (drive output stop)
A
Accel/Decel Ramp
Hold
When the terminal is switched ON, the drive momentarily pauses motor acceleration/
deceleration and holds the output frequency present at the time of the pause, and restarts
motor operation.
B
Overheat Alarm
(oH2)
Sets the drive to display an
oH2 [Drive Overheat Warning]
alarm when the input
terminal is ON. The alarm does not have an effect on drive operation.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV