Note:
•
The RUN light on the keypad will flash if the Run command is entered when the frequency reference is 0 Hz or below the value set in
E1-09 [Minimum Output Frequency]
. Examine the setting for the frequency reference input and enter a value more than or equal to the
E1-09
value.
0 : Keypad
Use the keypad to enter the frequency reference.
The frequency reference can be changed by using
and
on the keypad.
1 : Digital Input
Use the MFAI terminals A1, A2, and A3 to input an analog frequency reference with a voltage or current input
signal.
•
Voltage Input
Refer to this table to use a voltage signal input to one of the MFAI terminals.
Table 11.9 Frequency Reference Voltage Input
Termi
nal
Terminal Signal
Level
Parameter Settings
Note
Signal Level
Selection
Function
Selection
Gain
Bias
A1
0 - 10 V
H3-01 = 0
H3-02 = 0
[Frequency
Reference]
H3-03
H3-04
-
-10 - 10 V
H3-01 = 1
A2
0 - 10 V
H3-09 = 0
H3-10 = 0
[Frequency
Reference]
H3-11
H3-12
Set DIP switch S1 to
“
V
”
for voltage input.
-10 - 10 V
H3-09 = 1
A3
0 - 10 V
H3-05 = 0
H3-06 = 0
[Frequency
Reference]
H3-07
H3-08
Set DIP switch S4 to
“
AI
”
for analog input.
-10 - 10 V
H3-05 = 1
Figure 11.7 Example of Setting the Frequency Reference with a Voltage Signal to Terminal A1
Note:
Use this diagram also when wiring terminals A2 and A3.
•
Current Input
Refer to this table to use a current signal input to one of the MFAI terminals.
Termi
nal
Signal Level
Parameter Settings
Note
Signal Level
Selection
Function
Selection
Gain
Bias
A2
4 mA to 20 mA
H3-09 = 2
H3-10 = 0
[Frequency
Reference]
H3-11
H3-12
Set DIP switch S1 to
“
I
”
for current input.
0 - 20 mA
H3-09 = 3