662
YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
Logical Operation Selection
Logical Operation Expression
Logical Operation Notation
H2-61, H2-64, H2-67, H2-70
4
A=B
A=B
5
A != B
6
AND(A, )
7
OR(A, )
8
-
On
Note:
•
You cannot set
H2-01 to H2-05 = 1xx [Inverse Output of xx]
when using the function to output logical operation results.
•
H2-60, H2-63, H2-66, H2-69, and H2-72
cannot be set to
20 to 2F [External Fault]
.
•
Set
H2-60, H2-63, H2-66, H2-69, and H2-72 = F
when not using the terminal. However, the Through Mode function is not supported.
■
H2 MFDO Parameters
H2-01: Term M1-M2 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-01
(040B)
Term M1-M2
Function Selection
Selects the function assigned to MFDO terminal M1-M2.
21
(0 - 1FF)
Note:
Set this parameter to
F
when not using the terminal or to use the terminal in through mode.
H2-02: Term M3-M4 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-02
(040C)
Term M3-M4
Function Selection
Selects the function assigned to MFDO terminal M3-M4.
0
(0 - 1FF)
Note:
Set this parameter to
F
when not using the terminal or to use the terminal in through mode.
H2-03: Term M5-M6 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-03
(040D)
Term M5-M6
Function Selection
Sets the function for MFDO terminal M5-M6.
2
(0 - 1FF)
Note:
Set this parameter to F when not using the terminal or to use the terminal in through mode.
H2-04: Term P1-C1 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-04
(040E)
Term P1-C1 Function
Selection
Sets the function for MFDO terminal P1-C1.
6
(0 - 1FF)
Note:
Set this parameter to F when not using the terminal or to use the terminal in through mode.
H2-05: Term P2-C2 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-05
(040F)
Term P2-C2 Function
Selection
Sets the function for MFDO terminal P2-C2.
10
(0 - 1FF)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV