YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
663
Note:
Set this parameter to F when not using the terminal or to use the terminal in through mode.
H2-06: Watt Hour Output Unit Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-06
(0437)
Watt Hour Output
Unit Selection
Sets the unit for the output signal when
H2-01 to H2-05 = 39 [MFDO
Function Selection = Watt Hour Pulse Output]
.
0
(0 - 4)
This output is input to the Watt hour meter or PLC via a 200 ms pulse signal. Each pulse is output by the kWh unit
selected by
H2-06
.
Figure 11.58 Example MFDO when Set for Watt Hours
Note:
•
Watt hours are not counted when the power value is a negative value (regenerative state).
•
Stores the Watt hours while the control power supply to the drive is operating. The Watt hour count is reset when the control power is
cut because of a momentary power loss or other reason.
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
H2-07: Modbus Register 1 Address Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-07
(0B3A)
Modbus Register 1
Address Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO
terminal.
0001
(0001 - 1FFF)
Sets
H2-07
with the address of the register that is output to
Modbus Reg 1 Status Satisfied [H2-01 to H2-05 = 62]
and sets
H2-08
with the bit value.
H2-08: Modbus Register 1 Bit Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-08
(0B3B)
Modbus Register 1
Bit Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO
terminal.
0000
(0000 - FFFF)
Sets
H2-07
with the address of the register that is output to
Modbus Reg 1 Status Satisfied [H2-01 to H2-05 = 62]
and sets
H2-08
with the bit value.
H2-09: Modbus Register 2 Address Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-09
(0B3C)
Modbus Register 2
Address Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO
terminal.
0001
(0001 - 1FFF)
Sets
H2-09
with the address of the register that is output to
Modbus Reg 2 Status Satisfied [H2-01 to H2-05 = 63]
and sets
H2-10
with the bit value.