664
YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
H2-10: Modbus Register 2 Bit Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-10
(0B3D)
Modbus Register 2
Bit Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO
terminal.
0000
(0000 - FFFF)
Sets
H2-09
with the address of the register that is output to
Modbus Reg 2 Status Satisfied [H2-01 to H2-05 = 63]
and sets
H2-10
with the bit value.
H2-20: Comparator 1 Monitor Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-20
(1540)
Comparator 1
Monitor Selection
Sets the monitor number for comparator 1. Set the
x-xx
part of the
Ux-xx
[Monitor]
. For example, set
x-xx
to 102 to monitor
U1-02 [Output
Frequency]
.
102
(000 - 999)
Note:
•
Refer to
H2-xx = 66 and 67 [MFDO Function Select = Comparator1 and Comparator2]
for more information about the comparator
function.
•
The configurable monitor changes when the control method changes.
H2-21: Comparator 1 Lower Limit
No.
(Hex.)
Name
Description
Default
(Range)
H2-21
(1541)
Comparator 1 Lower
Limit
Sets the lower limit detection level for comparator 1 when the full scale
analog output for the monitor selected in
H2-20 [Comparator 1 Monitor
Selection]
is the 100% value.
0.0%
(0.0 - 300.0%)
Note:
Refer to
H2-xx = 66 and 67 [MFDO Function Select = Comparator1 and Comparator2]
for more information about the comparator
function.
H2-22: Comparator 1 Upper Limit
No.
(Hex.)
Name
Description
Default
(Range)
H2-22
(1542)
Comparator 1 Upper
Limit
Sets the upper limit detection level for comparator 1 when the full scale
analog output for the monitor selected in
H2-20 [Comparator 1 Monitor
Selection]
is the 100% value.
0.0%
(0.0 - 300.0%)
Note:
Refer to
H2-xx = 66 and 67 [MFDO Function Select = Comparator1 and Comparator2]
for more information about the comparator
function.
H2-23: Comparator 1 Hysteresis
No.
(Hex.)
Name
Description
Default
(Range)
H2-23
(1543)
Comparator 1
Hysteresis
Sets the hysteresis level for comparator 1 when the full scale analog output
for the monitor selected in
H2-20 [Comparator 1 Monitor Selection]
is the
100% value.
0.0%
(0.0 - 10.0%)
Note:
Refer to
H2-xx = 66 and 67 [MFDO Function Select = Comparator1 and Comparator2]
for more information about the comparator
function.
H2-24: Comparator 1 On-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-24
(1544)
Comparator 1 On-
Delay Time
Sets the on-delay time for comparator 1.
0.0 s