YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
697
2 : Fast Stop (Use C1-09)
The drive stops the motor using the deceleration time set in
C1-09 [Fast Stop Time]
. Fault relay output terminal
MA-MC will turn ON, and MB-MC will turn OFF.
3 : Alarm Only
CE
appears on the keypad, and operation continues. The output terminal set for
Alarm [H2-01 to H2-05 = 10]
switches ON.
H5-05: Comm Fault Detection Selection
No.
(Hex.)
Name
Description
Default
(Range)
H5-05
(0429)
Comm Fault
Detection Selection
Sets the function that detects
CE [Modbus Communication Error]
issues
during MEMOBUS/Modbus communications.
1
(0, 1)
If the drive does not receive data from the master during the time set in
H5-09 [CE Detection Time]
, it will detect
a
CE
error.
0 : Disabled
Does not detect
CE
. The drive continues operation.
1 : Enabled
Detects
CE
. If the drive detects
CE
, it will operate as specified by the setting of
H5-04 [Communication Error
Stop Method]
.
H5-06: Drive Transmit Wait Time
No.
(Hex.)
Name
Description
Default
(Range)
H5-06
(042A)
Drive Transmit Wait
Time
Sets the time to wait to send a response message after the drive receives a
command message from the master.
5 ms
(0 - 65 ms)
Figure 11.82 Drive Transmit Wait Time
H5-09: CE Detection Time
No.
(Hex.)
Name
Description
Default
(Range)
H5-09
(0435)
CE Detection Time
Sets the detection time for
CE [Modbus Communication Error]
issues when
communication stops.
2.0 s
(0.0 - 10.0 s)
H5-10: Modbus Register 0025H Unit Sel
No.
(Hex.)
Name
Description
Default
(Range)
H5-10
(0436)
Modbus Register
0025H Unit Sel
Sets the unit of measure used for the MEMOBUS/Modbus communications
monitor register 0025H (output voltage reference monitor).
0
(0, 1)
0 : 0.1 V units