YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
607
E7-24: Motor 3 Motor Poles
No.
(Hex.)
Name
Description
Default
(Range)
E7-24
(1B75)
Motor 3 Motor Poles
Sets the number of poles for motor 3.
4
(2 - 48)
E7-25: Motor 3 Line-to-Line Resistance
No.
(Hex.)
Name
Description
Default
(Range)
E7-25
(1B76)
Motor 3 Line-to-Line
Resistance
Sets the line-to-line resistance for motor 3 stator windings.
Determined by o2-04
(0.000 - 65.000 Ω)
E7-31: Motor 3 Rated Power
No.
(Hex.)
Name
Description
Default
(Range)
E7-31
(1B7C)
Motor 3 Rated Power
(kW)
Sets the motor 3 rated power in 0.01 kW. (1 HP = 0.746 kW)
Determined by o2-04
(0.00 - 650.00 kW)
◆
F: Options
F parameters
are used to set option cards, which function as interfaces for encoders, analog I/O, digital I/O, and
fieldbus communication.
■
F1: PG Option Setup (Encoder)
F1 parameters
are used to set the operation of and protective function for the encoder option card. The following
table lists the setting parameters available for each option card.
Refer to the instruction manual packaged with the encoder option card for more information about installing,
wiring, and setting the encoder option cards.
WARNING
Sudden Movement Hazard. Do test runs and examine the drive to make sure that command references are
configured correctly. If you set the command reference incorrectly, it can cause death, serious injury, or equipment damage from
unwanted motor rotation.
WARNING
Sudden Movement Hazard. Conduct proper host controller safety design to prevent motors from running
uncontrolled when there is a loss of speed feedback. The motor has a potential to run uncontrolled.
Table 11.18 Encoder Option Card Setting Parameters
Setting Parameter
Encoder Option Card
PG-B3
PG-X3
PG-RT3
F1-01
x
x
-
F1-02
x
x
x
F1-03
x
x
x
F1-04
x
x
x
F1-05
x
x
x
F1-06
x
x
-
F1-08
x
x
x
F1-09
x
x
x
F1-10
x
x
x
F1-11
x
x
x
F1-12
x
x
-
F1-13
x
x
-
F1-14
x
x
x
F1-20
-
x
-
F1-21
x
x
-
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV