6.6 Internal Torque Limits
6-22
6.6
Internal Torque Limits
You can limit the torque that is output by the Servomotor.
If you use internal torque limits, the maximum output torque will always be limited to the speci-
fied forward torque limit (Pn402) and reverse torque limit (Pn403).
Note: If you set a value that exceeds the maximum torque of the Servomotor, the torque will be limited to the maxi-
mum torque of the Servomotor.
•
Rotary Servomotors
*
Set a percentage of the rated motor torque.
Note: If the setting of Pn402 or Pn403 is too low, the torque may be insufficient for acceleration or deceleration of
the Servomotor.
•
Linear Servomotors
*
Set a percentage of the rated motor force.
Note: If the setting of Pn483 or Pn484 is too low, the force may be insufficient for acceleration or deceleration of the
Servomotor.
Pn402
Forward Torque Limit
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 800
1%
*
800
Immediately Setup
Pn403
Reverse Torque Limit
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 800
1%
*
800
Immediately Setup
Pn483
Forward Force Limit
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 800
1%
*
30
Immediately Setup
Pn484
Reverse Force Limit
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 800
1%
*
30
Immediately Setup
t
Pn403
Pn402
t
Without Internal Torque Limits
(Output to the maximum torque is possible.)
Maximum torque
Speed
Torque limit
Speed
With Internal Torque Limits
t
Pn484
Pn483
t
Without Internal Torque Limits
(Output to the maximum force is possible.)
Speed
With Internal Force Limits
Maximum force
Speed
Force limit