8.10 Vibration Suppression
8.10.4 Operating Procedure
8-56
3.
Click the
Import
Button or click
and
Button to manually adjust the set frequency.
When you click the
Import
Button, the residual vibration frequency in the Servomotor is read as the
set frequency. (The frequency can be read only when the residual vibration frequency is between 1.0
and 100.0.)
4.
Click the
Set
Button.
If the vibration is not eliminated, use the
and
Buttons for the set frequency to fine-tune the
value and click the
Set
Button again.
Click the
Reset
Button during adjustment to restore the setting to its original value. The status from
before when adjustment was started will be restored.
Frequency detection will not be performed if there is no vibration or if the vibration frequency
is outside the range of detectable frequencies. If a vibration frequency is not detected, pro-
vide a means of measuring the vibration frequency.
No settings related to vibration suppression are changed during operation.
If the Servomotor does not stop within approximately 10 seconds after changing the setting,
an update timeout will occur. The setting will be automatically returned to the previous value.
Important