15.2 Alarm Displays
15.2.3 INDEXER Module Alarm Displays and Troubleshooting
15-47
15
Maintenance
*1.
These alarms can be reset, but a Canceled Program Table Error (E44E) will occur the next time you attempt to
start program table operation, so program table operation will not be possible.
*2.
These alarms can be reset, but it is possible that the ZONE signals (POUT0 to POUT7) will be output incorrectly.
When using the ZONE table, correct the ZONE table without resetting.
*3.
These alarms can be reset, but a Canceled JOG Speed Table Error (E46E) will occur the next time you attempt
to start JOG speed table operation, so JOG speed table operation will not be possible.
E23A
A.AEF
Insufficient Reg-
istration Dis-
tance Alarm
The registration dis-
tance was shorter
than the deceleration
distance when the /
RGRT signal went
ON to start registra-
tion operation. (The
current position will
exceed the position
specified by registra-
tion.)
Either increase the reg-
istration distance or
reduce the decelera-
tion distance (increase
the deceleration rate).
The registration dis-
tance can be set by
executing the RDST
command or changing
the RDST parameter in
the program table.
The deceleration rate
can be changed by
executing the DEC
command or changing
parameter PnB2B.
Gr.1
Available
Continued from previous page.
Serial
Command
Negative
Response
Alarm
Number
Alarm Name
Meaning
Corrective Action
Servo-
motor
Stop
Method
Alarm
Reset