7.2 Applied Operation
7 -39
7.2.9 Initializing User Constant Settings
This function is used when returning to the standard settings (factory settings) after changing
user constant settings.
Initialize the user constant settings with the servo OFF.
Follow the procedure below to initialize user constant settings.
Using the Hand-held Digital Operator
1.
Press the DSPL/SET Key to select the auxiliary function mode.
2.
Select the user constant Fn005.
Press the Left or Right Cursor Key to select the digit.
Press the Up or Down Cursor Key to change the value.
3.
Press the DATA/ENTER Key, and the display will be as shown below.
4.
Press the DSPL/SET Key, and the display will be as shown below. The user constants will
be initialized.
Flashing for
one second
Flashing during
initialization
End
5.
Press the DATA/ENTER Key to return to the auxiliary function mode display.
This completes the initialization of user constant settings.