Physical Installation 1 - 9
Option U
Enable Embedded Serial Communications: A no cost option. The Drive in a Bypass unit is capable of network communications
via one of 3 embedded protocols. Specifying option U will enable the Siemens APOGEE protocol and provide the necessary
parameter settings and wiring (jumpers) to be network ready when delivered (Project specific H5-0X parameters are setup by
the user).
Option V
Enable Embedded Serial Communications: A no cost option. The Drive in a Bypass unit is capable of network communications
via one of 3 embedded protocols. Specifying option U will enable the Modbus protocol and provide the necessary parameter
settings and wiring (jumpers) to be network ready when delivered (Project specific H5-0X parameters are setup by the user).
Option W
Engraved Plastic Nameplate: An enclosure identification nameplate to carry the controlled equipment “tag number”.
Option X
3% DC Bus Reactor: Attenuates harmonic distortion by limiting the rate of rise of the input current. The bus reactor is wired
to the Drive (+1) and (+2) DC bus terminals to provide the equivalent impedance of a 3% input reactor. This option is only
used on the low end of the horsepower range where DC bus reactors are not a standard Drive component (25 HP and below @
208 VAC, 25 HP and below @ 240 VAC, and 30 HP and below @ 480 VAC.)
Option Y
LCD Keypad: Offers 5 lines of display with 16 characters on each line for expanded data presentation capability in English (or
other language) format.
Option Z
5% DC Bus Reactor: Attenuates harmonic distortion by limiting the rate of rise of the input current. The bus reactor is wired
to the Drive (+1) and (+2) DC bus terminals to provide the equivalent impedance of a 5% input reactor. This option is only
used on the low end of the horsepower range where DC bus reactors are not a standard Drive component (25 HP and below @
208 VAC, 25 HP and below @ 240 VAC, and 30 HP and below @ 480 VAC.)
Summary of Contents for E7LBA002
Page 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Page 8: ...Introduction vi Notes ...
Page 12: ...Table of Contents x Notes ...
Page 54: ...Electrical Installation 2 22 Wiring Diagram ...
Page 55: ...Electrical Installation 2 23 ...
Page 87: ...Start Up and Operation 4 9 Notes ...
Page 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Page 248: ...Capacity Related Parameters B 6 Notes ...
Page 279: ...Communications D 27 Note ...
Page 280: ...Communications D 28 ...
Page 292: ...Spare Parts F 6 ...
Page 304: ...Index 12 ...
Page 305: ......