Parameters A - 18
Analog Outputs
H4-06
Terminal AM Bias Setting
Terminal AM Bias
Sets terminal AM output voltage (in percent of 10V)
when selected monitor is at 0% output.
–110.0 to
110.0
0.0%
Programming
H4-07
Terminal FM Signal Level
Selection
AO Level Select1
0: 0 - 10 VDC
2: 4-20 mA*
0 or 2
0
Programming
H4-08
Terminal AM Signal Level
Selection
AO Level Select2
0: 0 - 10 VDC
2: 4-20 mA*
* An analog output of 4 - 20 mA can not be used with
the standard terminal board. Therefore an optional
terminal board (with shunt connector CN15) is needed.
0 or 2
0
Programming
Serial Com Setup
H5-01
Drive Node Address
Serial Comm Adr
Selects drive station node number (address) for
terminals R+, R-, S+, S-.*
An address of “0” disables serial com.
0 to 20
(H5-08=0)
0 to FF
(H5-08=1)
0 to 63
(H5-08=2)
1F #
Programming
H5-02
Communication Speed Selection
Serial Baud Rate
Selects the baud rate for terminals R+, R-, S+ and S-.*
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud (APOGEE FLN)
3: 9600 Baud (Metasys N2)
4: 19200 Baud
0 to 4
3
Programming
H5-03
Communication Parity Selection
Serial Com Sel
Selects the communication parity for terminals R+, R-,
S+ and S-.*
0: No Parity
1: Even Parity
2: Odd Parity
0 to 2
0
Programming
H5-04
Stopping Method after
Communication Error
Serial Fault Sel
Selects the stopping method when a communication
error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
4: Run at d1-04 - available when H5-08=
“1: N2 METASYS” or “2: FLN APOGEE”
0 to 3
3
Programming
H5-05
Communication Error Detection
Selection
Serial Flt Dtct
Enables or disables the communications timeout
detection function.
0: Disabled - A communications loss will NOT cause a
communications fault.
1: Enabled - If communications are lost for more than
the time specified in parameter H5-09,
a communications fault will occur.
0 or 1
1
Programming
H5-06
Drive Transmit Wait Time
Transmit WaitTIM
Sets the time from when the drive receives data to when
the drive sends data.
5 to 65
5ms
Programming
H5-07
RTS Control Selection
RTS Control Sel
Enables or disables “request to send” (RTS) control:
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)
0 or 1
1
Programming
H5-08
Communication Protocol
Selection
Protocol Select
Selects the communication protocol.
0: Memobus (Modbus)
1: N2 (Metasys)
2: FLN (APOGEE)
0 to 2
0
Programming
H5-09
Communication Error
Detection Time
CE Detect Time
Determines how long communications must be lost
before a fault is annunciated. Works in conjunction with
parameters H5-05 and H5-04.
0 to 10.0
(H5-08=0)
0 to 10.0
(H5-08=1)
0 to 90.0
(H5-08=2)
2.0sec
Programming
Denotes that parameter can be changed when the drive is running.
* After these parameters are changed, drive power must be cycled before the changes will take effect.
# Hex, see page A-30.
Table A.1 Parameter List (Continued
)
Parameter
No.
Parameter Name
LCD Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location
Summary of Contents for E7LBA002
Page 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Page 8: ...Introduction vi Notes ...
Page 12: ...Table of Contents x Notes ...
Page 54: ...Electrical Installation 2 22 Wiring Diagram ...
Page 55: ...Electrical Installation 2 23 ...
Page 87: ...Start Up and Operation 4 9 Notes ...
Page 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Page 248: ...Capacity Related Parameters B 6 Notes ...
Page 279: ...Communications D 27 Note ...
Page 280: ...Communications D 28 ...
Page 292: ...Spare Parts F 6 ...
Page 304: ...Index 12 ...
Page 305: ......