Communications D - 20
APOGEE FLN Point Database
APOGEE FLN Point List Summary
This database is for APOGEE FLN Application 2721 and features 97 logical points: 29 Logical Analog Inputs (LAI), 35 Log-
ical Analog Outputs (LAO), 19 Logical Digital Inputs (LDI) and 14 Logical Digital Outputs (LDO). These points configure,
control or monitor the operation of the Drive.
Information to consider when referencing this table:
1.
Points not listed are not used in this application.
2.
A single value in a column means that the value is the same in English units and in SI units.
3.
Point numbers that appear in brackets, e.g. {03}, can be unbundled at the field panel.
Table D.13 APOGEE FLN Application 2721 Point Number Summary
Point
Number
Point
Type
Point Name
Factory Default
(SI Units)
Engr. Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
E7
Parameter
01
LAO
CTLR ADDRESS
31
–
1
0
–
–
H5-01
02
LAO
APPLICATION
–
–
1
0
–
–
–
{03}
LAI
FREQ OUTPUT
0
HZ
0.01
0
–
–
U1-02
{04}
LAI
PCT OUTPUT
0
PCT
0.01
0
–
–
–
{05}
LAI
SPEED
0
RPM
0.01
0
–
–
–
{06}
LAI
CURRENT
0
AMPS (A)
0.01
0
–
–
U1-03
{07}
LAI
TORQUE
0
PCT
0.1
0
–
–
–
{08}
LAI
POWER
0
KW
0.1
0
–
–
U1-08
{09}
LAI
DRIVE TEMP
0
DEG F / C
1
0
–
–
U1-41
{10}
LAI
DRIVE KWH
0
KWH
0.1
0
–
–
U1-29
{11}
LAI
MWH
0
MWH
1
0
–
–
U1-30
{12}
LAI
RUN TIME
0
HRS
1
0
–
–
U1-13
{13}
LAI
DC BUS VOLT
0
PCT
1
0
–
–
U1-07
{14}
LAI
AC OUT VOLT
0
VOLTS (V)
0.1
0
–
–
U1-06
15
LAI
PAR N9.01
0
AMPS (A)
0.01
0
–
–
N9-01
{16}
LAI
RUN TIMEX10K
0
10K HR
1
0
–
–
U1-13
{17}
LAI
FAULT CODE
0
–
1
0
–
–
U2-01
{18}
LDI
MINOR FLT
NO FLT
–
1
0
FAULT
NO FLT
U1-12 (Bit 6)
{19}
LDI
MAJOR FLT
NO FLT
–
1
0
FAULT
NO FLT
U1-12 (Bit 7)
20
LAO
OVRD TIME
1
HRS
1
0
–
–
–
{21}
LDI
FWD.REV
FWD
–
1
0
REV
FWD
U1-12 (Bit 2)
{22}
LDO
CMD REV.STOP
STOP
–
1
0
REV
STOP
–
{23}
LDI
RUN.STOP
STOP
–
1
0
RUN
STOP
U1-12 (Bit 0)
{24}
LDO
CMD RUN.STOP
STOP
–
1
0
FWD
STOP
–
{25}
LDI
ZERO SPEED
OFF
–
1
0
ON
OFF
U1-12 (Bit 1)
{26}
LDI
SPEED AGREE
NO AGR
–
1
0
AGREE
NO AGR
U1-12 (Bit 4)
{27}
LDI
DRIVE READY
NOTRDY
–
1
0
READY
NOTRDY
U1-12 (Bit 5)
{28}
LDI
LOC.REM MON
REMOTE
–
1
0
LOCAL
REMOTE
–
{29}
LDO
DAY.NGT
DAY
–
1
0
NGT
DAY
–
30
LAO
CURRENT LIM
0
AMPS (A)
0.01
0
–
–
E2-01
31
LAO
ACCEL TIME 1
0
SEC
0.1
0
–
–
C1-01
32
LAO
DECEL TIME 1
0
SEC
0.1
0
–
–
C1-02
33
LDO
LOCK PANEL
UNLOCK
–
1
0
LOCK
UNLOCK
–
35
LDO
RUN ENABLE
STOP
–
1
0
ENABLE
STOP
–
36
LAO
STALL PRE RN
90
PCT
30
0
–
–
L3-06
37
LAO
STALL PRE AC
120
PCT
1
0
–
–
L3-02
38
LAO
FREQ UP LIM
100
PCT
0.1
0
–
–
D2-01
Summary of Contents for E7LBA002
Page 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Page 8: ...Introduction vi Notes ...
Page 12: ...Table of Contents x Notes ...
Page 54: ...Electrical Installation 2 22 Wiring Diagram ...
Page 55: ...Electrical Installation 2 23 ...
Page 87: ...Start Up and Operation 4 9 Notes ...
Page 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Page 248: ...Capacity Related Parameters B 6 Notes ...
Page 279: ...Communications D 27 Note ...
Page 280: ...Communications D 28 ...
Page 292: ...Spare Parts F 6 ...
Page 304: ...Index 12 ...
Page 305: ......