Table A.6 Drive Specifications
Item
Specifications
Efficiency
<1> Adjustments (e.g., to parameters) are required after auto-tuning.
<2> When using the momentary power loss compensation function, an uninterruptible power supply unit option is required for the control power
supply.
<3> An option card and additional wiring are required to use the communications function. For CP-215 communication, an optional expansion PLC
board is required.
Long Term Storage of Drives on page 71
for details on the long term storage of the drives.
European Standards on page 220
for details on compliance with CE standards.
Approx. 97% (At rated motor speed, 100% load)
Power Factor
Min. 0.95 (At motor rated speed, 100% load)
Cooling Method
Forced air-cooling by fan (with failure detection)
Control
Control Method
Open Loop Vector Control (OLV), Closed Loop Vector Control (CLV), V/f control (for multiple motor
operation), Closed Loop Control for SM (optional)
Main Circuit
Voltage-type PWM control with multiple outputs connected in series
(Power Cell: 3-level output)
Frequency Control
Range
0.01 to 120 Hz
Frequency Control
Accuracy
±
0.5%
Analog Input
Resolution
0.03 Hz
Accel/Decel Time
0.1 to 6000 s
Torque Accuracy
±
5% (OLV),
±
3% (CLV)
Overload Tolerance
Continuous rated current 100%, overload tolerance 110% for 1 minute and 120% for 15 seconds
Momentary Power
Loss Compensation
Time
Max. 2 seconds
Main Control
Functions
Torque control, Droop control, Speed/torque control switch, Momentary power loss compensation, Speed
search, Overtorque detection, Torque limit, 17-step speed (max.), Accel/decel time switch, S-curve accel/decel,
Auto-tuning (rotational, stationary), Dwell, Cooling fan on/ off, Slip compensation, Torque compensation,
Frequency jump, Upper/lower limits for frequency reference, DC injection braking at start and stop, PID
control (with sleep function), MEMOBUS communication (RS-485, max. 115.2 kbps), Fault retry
Protective Functions
Overcurrent, Overvoltage, Undervoltage, Output ground fault, Output open-phase, Overload, Cooling-fan
error, Transformer overheat, Motor overheat, etc.
PLC Functions (Optional)
Expansion PLC board
Maintenance Tools
USB: DriveWizard Plus MV
Communications
(Optional)
• RS-485: MEMOBUS (Modbus)
• One of the following hardware; PROFIBUS-DP, DeviceNet, Ethernet, or CP-215 can be installed.
Input Transformer
Class H dry type, -5%/N/+5% tap, secondary multi-phase winding
Temperature Protection
Power Cells: protected by thermistor for temperature
Transformer: protected by temperature monitor (PT100
Ω
) and thermo switches
Main
ta
inab
ili
ty/
En
vir
o
n
men
ta
l
Control Panel
Status display, Fault display, Parameter setting, Parameter reference
Main Circuit
Power Cell construction
Protection Design
IP40 (simplified dustproof type)
Ambient
Temperature,
Relative Humidity
-5
°
C to +40
°
C with derating, 85% RH maximum (no condensation)
Storage Temperature
-20
°
C to +60
°
C (for very short term when handling)
Atmosphere
General environmental conditions, free from dust and corrosive gases
Altitude: 0 to 2000 m
Panel
S
p
ecification
s
Painting
Munsel 5Y7/1 semi gloss for inner and outer faces
Form
Made of enclosing steel sheets, vertical standalone type, front maintenance type
Applicable Standards
JIS, JEM, JEC
Summary of Contents for FSDrive-MV1000 Series
Page 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...