C.4 MEMOBUS/Modbus Setup Parameters
YASKAWA ELECTRIC
TOEP C710687 02B FSDrive-MV1000 Instructions
229
M
EMOBUS
/Mo
dbu
s
Co
m
m
u
ni
ca
ti
on
s
C
n
H5-05: Communication Fault Detection Selection
Enables or disabled the communication error (CE) detection for MEMOBUS/Modbus communications.
Setting 0: Disabled
No communication error detection. The drive continues operation.
Setting 1: Enabled
If communication is lost for more than the time set in H5-09, then a CE fault will be triggered and the drive will operate
as determined by parameter H5-04.
n
H5-06: Drive Transmit Wait Time
Sets the time the drive waits after receiving data from a master until responding data.
Figure C.4
Figure C.4 Drive Transmit Wait Time Setting
n
H5-07: RTS Control Selection
Enables or disables RTS control.
Setting 0: Disabled. RTS is always on.
Setting 1: Enabled. RTS switches while sending.
Use this setting when using RS-485 signals for communications.
n
H5-09: CE Detection Time
Sets the time the communications must be lost before the drive triggers a CE fault. Adjustment may be needed when
networking several drives.
No.
Name
Setting Range
Default
H5-05
Communication Fault Detection Selection
0 or 1
1
No.
Name
Setting Range
Default
H5-06
Drive Transmit Wait Time
5 to 65 ms
5 ms
No.
Name
Setting Range
Default
H5-07
RTS Control Selection
0 or 1
1
No.
Name
Setting Range
Default
H5-09
CE Detection Time
0.0 to 10.0 s
2.0 s
Command message
Response message
Command message
Master→Drive
Master→Drive
Drive→Master
Time
24 bit length
H5-06 setting
Summary of Contents for FSDrive-MV1000 Series
Page 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...