2.2 Mechanical Installation
YASKAWA ELECTRIC
TOEP C710687 02B FSDrive-MV1000 Instructions
43
Mech
ani
c
al
In
st
al
la
ti
on
2
u
Installation Space
shows the installation distance required to maintain sufficient space for airflow and wiring.
Note:
If the installation space for the drive is restricted and the space indicated in the figures below cannot be secured, contact your
Yaskawa representatives or the nearest Yaskawa sales office.
Figure 2.1
Figure 2.1 Drive Installation Space
Table 2.2 Precautions on Installation Space
A – Min. 1000 mm
D – Min. 600 mm
B – Min. 30 mm
E – Max. 800 mm
C – Min. 2000 mm
Installation
Space
Details
A (Top)
The drive requires sufficient space at the top for the replacement of the cooling fans and to cool the drive. Air is
expelled through the cooling fans on top of the drive. If the cooling fans are too close to the ceiling, the air that has been
expelled may be drawn back into the drive and reduce the cooling performance.
B (Sides)
Although side-by-side installation with other panels is possible, the factory recommends ensuring at least 30 mm
spacing is available between panels.
C (Front)
Sufficient space is required to allow Power Cells to be drawn out and placed on the lifter to move them during
replacement.
D (Rear)
Sufficient working space is required to route the cables and to install anchors on the back of the drive.
E (Front)
Sufficient working space is required to open the door.
B
C
D
E
A
B
Front views
Side view
Door opening dimension
Door opening dimension
Front
Rear
Asia
Summary of Contents for FSDrive-MV1000 Series
Page 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...