42
YASKAWA ELECTRIC
TOEP C710687 02B FSDrive-MV1000 Instructions
2.2 Mechanical Installation
2.2 Mechanical Installation
This section outlines specifications, procedures, and the environment for proper mechanical installation of the drive.
u
Installation Environment
Install the drive in an environment matching the specifications in
to help prolong the optimum performance life
of the drive.
Table 2.1 Installation Environment
NOTICE:
Never install ducts in the air exhaust system. Making modifications, such as connecting air exhaust ducts to the drive panel's
cooling fan, could reduce the cooling airflow and result in an abnormal rise in temperature or drive failure. Do not connect air exhaust
ducts.
NOTICE:
Take measures to prevent salt-bearing atmospheric air, rain, and dust getting into the switch room. Insulation is impaired and
metals are corroded by absorption of moisture and salt damage, and this can cause the drive to malfunction. Also install an air
conditioner or ventilation system with sufficient capacity to prevent all potential damage to the drive and the other devices in the switch
room, and maintain an ambient temperature of no higher than 40°C and a humidity of no greater than 85% (Yaskawa recommends the
installation of an air conditioner).
NOTICE:
Observe the following precautions when installing the drive.
When installing the drive take care to prevent metal chips from drilling, oil, water, from and so on getting stuck to the drive or inside it.
And when the installation work is completed, check thoroughly to ensure that no tools or unused parts have been left inside the panel,
and that there are no foreign objects or obstructions on or around parts where power flows, at the air filters, or on the ventilation louver
on the top of the drive. Failure to comply could result in damage to the panel.
Note: 1.
Operate the drive with the fan cover attached on top of the panel. If the installation space is limited and the fan cover must be
removed, contact your Yaskawa representative or the nearest Yaskawa office.
2.
If the drive must be installed in a location subject to a high level of vibration caused by machines such as cranes, contact your
Yaskawa representatives or the nearest Yaskawa sales office. The drive generates electrical interference, including radio interference.
This should be considered when selecting the installation location.
3.
Please comply with the law of the relevant country when installing the drive panel. For details, contact your Yaskawa representative.
Environment
Conditions
Installation Area
Indoors
Enclosure Type
IP40 (simplified dustproof type)
Ambient
Temperature
-5
°
C to +40
°
C
If the ambient temperature changes greatly, condensation may occur. When installing the drive in such an
environment, take measures to prevent condensation, such as installing a space heater inside the drive. If a space
heater is required, contact your Yaskawa representative or the nearest Yaskawa sales office in advance.
Relative Humidity
85%RH max. (no condensing)
Storage
Temperature
-20
°
C to +60
°
C (for very short term when handling)
Refer to
when storing the drive for extended periods without applying power.
Surrounding Area
Install the drive in an area free from:
• oil mist and dust
• radioactive materials
• combustible materials
• chlorides
• direct sunlight
• harmful gases and liquids
metal shavings, oil, water, or other foreign materials
Altitude
0 to 2000 m
Pollution Degree
Level 2 or better
Summary of Contents for FSDrive-MV1000 Series
Page 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...