YASKAWA
TOEPC71061752B GA500 Drive Installation & Primary Operation
151
Drive Model
Fuse
Manufacturer:
Bussmann
Model
2021
FWH-90B
2030
FWH-100B
2042
FWH-150B
Drive Model
Fuse
Manufacturer:
Bussmann
Model
2056
FWH-200B
2070
FWH-200B
2082
FWH-225A
Table 14.8 Recommended Fuse: Three-Phase 400 V Class
Drive Model
Fuse
Manufacturer:
Bussmann
Model
4001
FWH-40B
4002
FWH-40B
4004
FWH-50B
4005
FWH-70B
4007
FWH-70B
4009
FWH-90B
4012
FWH-90B
Drive Model
Fuse
Manufacturer:
Bussmann
Model
4018
FWH-80B
4023
FWH-100B
4031
FWH-125B
4038
FWH-175B
4044
FWH-200B
4060
FWH-200B
◆
EMC Directive
Use drives with built-in EMC filters or install external EMC filters to the drive input side to
comply with the EMC Directive.
Drives with built-in EMC filters (models BxxxE, 2xxxE, 4xxxE) were tested in accordance with
European standard EN 61800-3:2004/A1:2012, and comply with the EMC Directive.
■
Install a Drive to Conform to the EMC Directive
Install drive models BxxxE, 2xxxE, and 4xxxE with this procedure to comply with the EMC
Directive when the drive is a single unit or installed in a larger device.
1.
Install the drive on a grounded metal plate.
2.
Wire the drive and motor.