YASKAWA
TOEPC71061752B GA500 Drive Installation & Primary Operation
153
A - Grounding surface (Remove
any paint or sealant.)
B - Enclosure panel
C - Metal plate
D - Drive
E -
Shielded wire
F -
Motor
G - Motor cable
H - Cable clamp
I -
Grounding wire
Figure 14.6 Install a Drive with a Built-in EMC Filter
5.
Connect an AC reactor or DC link choke to decrease harmonic distortion. Refer to
to select a DC link choke.
Note:
• To comply with EN 61000-3-2 on drive models 2001 to 2006, and 4001 to 4004, install a DC link choke.
• The terminal block for the drive main circuit and the terminal block for the DC link choke have different
shapes. The drive has a European-style terminal block, and the DC link choke has a round terminal block.
Correctly prepare the ends of the wiring.
Ground Wiring
WARNING
Electrical Shock Hazard. Do not remove covers or touch circuit boards while the drive is
energized. If you touch the internal components of an energized drive, it can cause serious injury or death.