YASKAWA
TOEPC71061752B GA500 Drive Installation & Primary Operation
179
■
E2-01: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E2-01
(030E)
Motor Rated
Current (FLA)
Sets the motor rated current in amps.
Determined by o2-
04, C6-01
(10% to 200% of
the drive rated
current)
Note:
•
If
E2-01 < E2-03 [Motor No-Load Current]
, the drive will detect
oPE02 [Parameter Range Setting Error]
.
•
When the drive model changes, the display units for this parameter also change.
–
0.01 A: B001 to B018, 2001 to 2042, 4001 to 4023
–
0.1 A: 2056 to 2082, 4031 to 4060
The value set for
E2-01
becomes the reference value for motor protection and the torque limit.
Enter the motor rated current written on the motor nameplate. Auto-Tuning the drive will
automatically set
E2-01
to the value input for
T1-04 [Motor Rated Current]
.
■
E5-03: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E5-03
(032B)
Motor Rated
Current (FLA)
Sets the PM motor rated current (FLA).
Determined by o2-
04, C6-01
(10% to 200% of
the drive rated
current)
Note:
When the drive model changes, the display units for this parameter also change.
•
0.01 A: B001 to B018, 2001 to 2042, 4001 to 4023
•
0.1 A: 2056 to 2082, 4031 to 4060
The drive automatically sets
E5-03
to the value input for
T2-06 [PM Motor Rated Current]
after
you do these types of Auto-Tuning:
•
PM Motor Parameter Settings
•
PM Stationary Auto-Tuning
•
PM StaTun for Stator Resistance
•
PM Rotational Auto-Tuning
■
E9-06: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E9-06
(11E9)
Motor Rated
Current (FLA)
Sets the motor rated current in amps.
Determined by
E9-01 and o2-04
(10% to 200% of
the drive rated
current)
Note:
When the drive model changes, the display units for this parameter also change.
•
0.01 A: B001 to B018, 2001 to 2042, 4001 to 4023
•
0.1 A: 2056 to 2082, 4031 to 4060
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV