YASKAWA
TOEPC71061752B GA500 Drive Installation & Primary Operation
29
■
Single Drive Installation Clearances
Use the clearances specified in
to install the drive. Make sure that there is sufficient
space for wiring and airflow.
A - 50 mm (2 in) minimum
between upper and lower
openings
B - 30 mm (1.18 in) minimum on
each side
C - 100 mm (3.94 in) minimum
above and below
D - Airflow direction
Figure 7.5 Installation Clearances for One Drive
■
Install Drives Side-by-Side
When you install drives side-by-side, set to
L8-35 = 1 [Installation Method Selection = Side-by-
Side Mounting]
.
Refer to the Technical Reference and derate the drives for the ambient temperature.