YASKAWA
TOEPC71061752B GA500 Drive Installation & Primary Operation
133
Code
Name
Causes
Possible Solutions
PWEr
DWEZ Password
Mismatch
The password set in the backup
operation with
qx-xx
[DriveWorksEZ Parameters]
and
rx-xx [DriveWorksEZ
Connections]
is incorrect.
Set the DWEZ PC software password
supplied by Yaskawa for the DWEZ
program user ID downloaded to the drive.
rdEr
Error Reading Data
You tried to back up the data when
o3-02 = 0 [Copy Allowed
Selection = Disabled]
.
Set
o3-02 = 1 [Enabled]
and back up again.
vAEr
Voltage Class, Capacity
Mismatch
The power supply specifications or
drive capacity parameter settings
are different between the keypad
and the drive.
1.
Make sure that drive model and the
value set in
o2-04 [Drive Model (KVA)
Selection]
agree.
2.
Restore the parameters.
vFyE
Parameters do not
Match
The parameters that are backed up
in the keypad and the parameters
in the drive are not the same.
1.
Restore or backup the parameter again.
2.
Verify the parameters.
14
European Standards
Figure 14.1 CE Mark
The CE Mark identifies that the product meets environmental and safety standards in the
European Union. Products manufactured, sold, or imported in the European Union must display
the CE Mark.
European Union standards include standards for electrical appliances (Low Voltage Directive),
standards for electrical noise (EMC Directive), and standards for machinery (Machinery
Directive).
This product displays the CE Mark in accordance with the Low Voltage Directive, the EMC
Directive, and the Machinery Directive.
Table 14.1 Harmonized Standards
European Directive
Harmonized Standard
CE Low Voltage Directive Compliance
2014/35/EU
EN 61800-5-1:2007
EMC Directive
2014/30/EU
EN 61800-3:2004/A1:2012
Machinery Directive
2006/42/EC
•
EN ISO 13849-1:2015 (PL e (Cat.III))
•
EN 62061:2005/A2:2015 (SILCL3)
•
EN 61800-5-2:2007
The customer must display the CE Mark on the final device containing this product. Customers
must verify that the final device complies with EU standards.