GPD315/V7 Modbus RTU Technical Manual TM 4325
Page
37
Set up for External Terminals Control
Table two indicates the functions or commands that can be accessed via serial communication,
external terminals, or the digital operator when the drive’s parameter n003 is set up for external
terminal control (n003 = 1). The “O” indicates that the function is Operable from that source, and
“n/a” indicates that the function is not available from that source.
Table 7-2: Set up for External Terminals Control
From
Data
Code
Bit
No.
Data Description
Function
Availability
0
Run Command
n/a
1
Forward / Reverse
n/a
2
External Fault
O
3
Fault Reset
O (1)
4
Multi-function Input Reference 1
O
5
Multi-function Input Reference 2
O
6
Multi-function Input Reference 3
O
7
Multi-function Input Reference 4
O
8
Multi-function Input Reference 5
O
9
Multi-function Input Reference 6
O
001h
A
Multi-function Input Reference 7
O
003h-
unused
-
008h
0
Multi-function Output 1 - Contact
O (4)
1
Multi-function Output 2 – Photo coupler 1
O (4)
2
Multi-function Output 3 – Photo coupler 2
O (4)
SERIAL
COMM.
009h
3-7
unused
-
Forward Run (2 wire); Run Command (3 wire)
O
Reverse Run (2 wire); Stop Command (3 wire)
O
Multi-function input terminal S3
O (2)
Multi-function input terminal S4
O (2)
Multi-function input terminal S5
O (2)
Multi-function input terminal S6
O (2)
EXTERNAL
TERMINALS
Multi-function input terminal S7
O (2)
Run Command
n/a
Stop Command
O (3)
Fault Reset
O (1)
DIGITAL
OPERATOR
Local / Remote
O (1)
Notes:
1.
Effective only when in the stopped condition.
2.
The availability of the multi-function input terminals vary depending upon the settings of
n052, n053, n054, n055, and n056 (the multi-function input settings). See technical
manual TM 4315.
3.
Effective only when n007 is “0”.
4.
Effective when n057, n058, and n059 are set to “18”.