2-3
DIGITAL OPERATOR
DESCRIPTION
KEY SEQUENCE
DISPLAY
Table 2-1. Open Loop Vector Startup Procedure - Continued
Set motor rated current.
(This can be obtained from
the nameplate of the motor.)
Press and hold
until n036 is
displayed on the digital operator.
Then press
.
Use the
&
keys until the
number in the display matches the motor
rated current.
Then press
.
DATA
ENTER
V
V
DATA
ENTER
V
Set the motor rated slip.
This can be calculated by
using the following formula:
Slip = (Ns-Nr) * P
120
Where:
Ns = Motor synch. speed
(2)
Nr = Motor rated speed
P = Number of motor poles
Example:
Slip = (1800 - 1725) * 4
120
Slip = 2.5
Press and hold
until n106 is
displayed on the digital operator.
Then press
.
Use the
&
keys until the
number in the display matches the calculated
slip value (see equation at left).
Then press
.
DATA
ENTER
V
V
DATA
ENTER
V
Prepare to test run the
drive from the Digital
Operator. Motor should be
disconnected from the load.
This will set the drive into the
“Local” mode and bring up
the motor current display.
Press and hold
several times until
the
LED is lit.
Press the
key once.
Display the drive’s output current by pressing
four times. Turn the Digital Operator
Pot all the way to the left (counter-clockwise.
DSPL
V
LO/RE
DSPL
PRGM
PRGM
PRGM
PRGM
LO/RE
LO/RE
IOUT
(1)
(1)
Summary of Contents for GPD315/V7-4X
Page 1: ...GPD 315 V7 and V7 4X Technical Manual...
Page 4: ......
Page 20: ...xvi...
Page 22: ......
Page 40: ...1 18...
Page 52: ...3 2...
Page 56: ...4 4...
Page 101: ...5 45 PID Block Diagram...
Page 130: ...A1 8...
Page 134: ...A3 2...
Page 136: ...A4 2...
Page 146: ...A6 6...
Page 150: ...A7 4...
Page 154: ...A8 4...
Page 158: ......
Page 160: ......