2-5
DIGITAL OPERATOR
DESCRIPTION
KEY SEQUENCE
DISPLAY
Table 2-1. Open Loop Vector Startup Procedure - Continued
Set the motor “no load
current” in the drive.
Motor no load current is set
as a percentage of motor
rated current. It is calculated
using the formula:
I
noload
*100 = n110
I
rated
Where:
I
noload
= Motor no load current
(measured in the
previous step)
I
rated
= Motor rated current
(from motor
nameplate)
Example:
2.5 * 100 = 60
4.2
Press the
key four times.
DSPL
This completes the startup.
Make further programming
changes as required.
Press the
key to get out of the
programming mode.
DSPL
(1)
The number in the display may be different than shown.
(2)
Motor synchronous speed can be calculated using the following formula:
120 x motor rated frequency
synch. speed =
number of motor poles
For 60 Hz Rated Motors
Poles
Synchronous Speed
2
3600 RPM
4
1800 RPM
6
1200 RPM
8
900 RPM
PRGM
PRGM
PRGM
PRGM
FREF
Press the
key.
DATA
ENTER
Press the
key.
Use the
&
keys until the
number in the display matches calculated no-
load current.
V
V
DATA
ENTER
Press the
key four times.
V
(1)
(1)
Summary of Contents for GPD315/V7-4X
Page 1: ...GPD 315 V7 and V7 4X Technical Manual...
Page 4: ......
Page 20: ...xvi...
Page 22: ......
Page 40: ...1 18...
Page 52: ...3 2...
Page 56: ...4 4...
Page 101: ...5 45 PID Block Diagram...
Page 130: ...A1 8...
Page 134: ...A3 2...
Page 136: ...A4 2...
Page 146: ...A6 6...
Page 150: ...A7 4...
Page 154: ...A8 4...
Page 158: ......
Page 160: ......