5-33
n001 : Parameter Selection / Initialization
Factory setting: 1
Range: 0 to 9
The following table shows which parameters can be programmed (displayed & changed) or only
displayed when n001 is selected.
By entering a “10” or an “11” into n001, all parameters in the Drive
will return to their factory settings.
Factory Configuration for
Parameter
Terminal
2-Wire Control
3-Wire Control
n050
S1
1 = Forward Run
1 = Start
n051
S2
2 = Reverse Run
2 = Stop
n052
S3
3 = External Fault (N.O.)
0 = Fwd/Rev Command
n053
S4
5 = Fault Reset
5 = Fault Reset
n054
S5
6 = Multi Step Ref. Cmd. A
6 = Multi Step Ref. Cmd. A
n055
S6
7 = Multi Step Ref. Cmd. B
7 = Multi Step Ref. Cmd. B
n056
S7
10 = JOG Selection
10 = JOG Selection
Know your application before using either Initialization function of n001 .
This parameter must be set to " 0 " to " 3 " for operation.
" 10 " = Factory 2-Wire Control Initialization (Maintained RUN Contact)
" 11 " = Factory 3-Wire Control Initialization (Momentary START/STOP Contact)
Entering either Initialization code resets all parameters to factory settings, and
automatically returns n001 setting to " 1 ". If the Drive is connected for 3-Wire
control and this parameter is set to " 10 " (2-Wire Control Initialization), the motor
may run in reverse direction WITHOUT A RUN COMMAND APPLIED. Equipment
damage or personal injury may result.
IMPORTANT
After " 10 " or " 11 " has been entered in n001 , the Motor Rated Current (n036 )
MUST BE REPROGRAMMED to the correct setting for the application.
5.21 RESET CODES: 2-WIRE, 3-WIRE INITIALIZATION
Setting
Function
0
n001 can be read and set;
n002 - n179 read only
1
n001 - n039 can be read and set
2
n001 - n067 can be read and set
3
n001 - n113 can be read and set
4
n001 - n179 can be read and set
5
n001 - n179 can be read and set
6
Clear Fault Record Only
7
Not Used
10
Initialization: 2-Wire control
11
Initialization: 3-Wire control
WARNING
CAUTION
Summary of Contents for GPD315/V7-4X
Page 1: ...GPD 315 V7 and V7 4X Technical Manual...
Page 4: ......
Page 20: ...xvi...
Page 22: ......
Page 40: ...1 18...
Page 52: ...3 2...
Page 56: ...4 4...
Page 101: ...5 45 PID Block Diagram...
Page 130: ...A1 8...
Page 134: ...A3 2...
Page 136: ...A4 2...
Page 146: ...A6 6...
Page 150: ...A7 4...
Page 154: ...A8 4...
Page 158: ......
Page 160: ......