SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
A - Drive Series
B - Maximum Applicable Motor Output
C - Rated Output Current
D - Software Version
E - Serial Number
◆
Write Automatically Backed-up Parameters to the Bypass
You can automatically back up parameters to the keypad connected to the bypass and write those parameters to a
different drive as specified by the settings of
o3-06 [Auto Parameter Backup Selection]
and
o3-07 [Auto Parameter
Backup Interval]
.
Note:
•
Set
o3-06 = 1 [Auto Parameter Backup Selection = Enabled]
in each bypass to which you will write the parameters.
•
This operation is not available when the parameters in the keypad and the parameters on the other bypasses are set to the same values.
1.
Connect the keypad to the bypass.
2.
Push
or
to select [Yes] and then push
.
3.
Push
or
to select [Yes] and then push
.
The keypad will show the
“
End
”
message when the write process is complete.