YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
255
■
F6-08: Comm Parameter Reset @Initialize
No.
(Hex.)
Name
Description
Default
(Range)
F6-08
(036A)
Comm Parameter Reset
@Initialize
Sets the function to initialize
F6-xx and F7-xx parameters
when the drive is initialized with
A1-03
[Initialize Parameters]
.
0
(0, 1)
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
Note:
When you use
A1-03
to initialize the drive, this setting will not change.
■
F6-14: BUS Error Auto Reset
No.
(Hex.)
Name
Description
Default
(Range)
F6-14
(03BB)
BUS Error Auto Reset
Sets the automatic reset function for
bUS [Option Communication Errors]
.
0
(0, 1)
0 : Disabled
1 : Enabled
■
F6-15: Comm. Option Parameters Reload
No.
(Hex.)
Name
Description
Default
(Range)
F6-15
(0B5B)
Comm. Option Parameters
Reload
Sets the update method when you change
F6-xx, F7-xx [Communication Options]
.
0
(0 - 2)
Note:
•
Set
F6-15 = 0, 1
to reload
F6-xx
,
F7-xx
.
•
Set
F6-15 = 0, 1
to reset the display on the keypad to
0
.
0 : Reload at Next Power Cycle
Restart the drive to update parameters.
1 : Reload Now
The changed parameters are updated without restarting the drive.
2 : Cancel Reload Request
Cancels
CyPo [Cycle Power to Accept Changes]
.
■
F7-01: IP Address 1
No.
(Hex.)
Name
Description
Default
(Range)
F7-01
(03E5)
IP Address 1
Sets the first octet of the IP Address for the device that is connecting to the network. Restart the drive
after you change this parameter.
192
(0 - 255)
Note:
When
F7-13 = 0 [Address Mode at Startup = Static]
:
•
Use parameters
F7-01 to F7-04 [IP Address 4]
to set the IP Address. Be sure to set a different IP address for each drive on the network.
•
Also set parameters
F7-01 to F7-12
.
■
F7-02: IP Address 2
No.
(Hex.)
Name
Description
Default
(Range)
F7-02
(03E6)
IP Address 2
Sets the second octet of the IP Address for the device that is connecting to the network. Restart the
drive after you change this parameter.
168
(0 - 255)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...