MFDO Setting Values
Selects the function configured to MFDO.
■
0: During Run
Setting Value
Function
Description
0
During Run
The terminal activates when you input a Run command and when the drive is outputting voltage.
Figure 5.46 Drive Running Time Chart
ON : Drive is running
The drive is receiving a Run command or outputting voltage.
OFF : Drive is stopping
■
1: Zero Speed
Setting Value
Function
Description
1
Zero Speed
The terminal activates when the output frequency <
E1-09 [Minimum Output Frequency]
.
E1-09: Minimum Output Frequency
Figure 5.47 Zero Speed Time Chart
ON : Output frequency <
E1-09
.
OFF : Output frequency
≥
E1-09
.
■
2: Speed Agree 1
Setting Value
Function
Description
2
Speed Agree 1
The terminal activates when the output frequency is in the range of the frequency reference ±
L4-02 [Speed Agree Detection Width]
.
Note:
The detection function operates in the two motor rotation directions.