10: Alarm
Setting Value
Function
Description
10
Alarm
The terminal activates when the drive detects a minor fault.
■
11: Fault Reset Command Active
Setting Value
Function
Description
11
Fault Reset Command
Active
The terminal activates when the drive receives the Reset command from the control circuit terminal, serial communications, or the
communication option.
■
12: Timer Output
Setting Value
Function
Description
12
Timer Output
Use this setting when the drive uses the timer function as an output terminal.
Note:
Refer to
Timer Function Operation on page 206
for more information.
■
13: Speed Agree 2
Setting Value
Function
Description
13
Speed Agree 2
The terminal activates when the output frequency is in the range of the frequency reference ±
L4-04 [Speed Agree Detection Width
(+/-)]
.
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency is in the range of “frequency reference
±
L4-04
”.
OFF : The output frequency is not in the range of “frequency reference
±
L4-04
”.
L4-04: Speed Agree Detection Width(+/-)
Figure 5.52 Speed Agree 2 Time Chart
■
14: User-Set Speed Agree 2
Setting Value
Function
Description
14
User-Set Speed Agree 2
The terminal activates when the output frequency is in the range of
L4-03 [Speed Agree Detection Level (+/-)]
±
L4-04 [Speed
Agree Detection Width (+/-)]
and in the range of the frequency reference ±
L4-04
.
Note:
The detection level set in
L4-03
is a signed value. The drive will only detect in one direction.
ON : The output frequency is in the range of “
L4-03
±
L4-04
” and the range of frequency reference
±
L4-04
.
OFF : The output frequency is not in the range of “
L4-03
±
L4-04
” or the range of frequency
reference
±
L4-04
.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...