2.3 Installation Positions and Clearances
36
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
◆
Enclosed Bypass Installation Position and Clearances
■
Installation Dimensions
Refer to the Dimension Drawing (DD.HB.x.xx.xx) packaged with the bypass for exterior and mounting dimensions
for your model.
■
Installation Position
Install the bypass vertically for sufficient cooling airflow.
A - Vertical installation
B - Horizontal installation
Figure 2.3 Installation Position
■
Single Enclosed Bypass Installation Clearances
Use the clearances specified in
to install the bypass. Make sure that there is sufficient space for wiring and
airflow.
A - 50 mm (2 in) minimum
B - 102 mm (4 in) minimum
C - 152 mm (6 in) minimum
D - Airflow direction
Figure 2.4 Single Bypass Installation
*1
This is the distance from a component or mounting bracket that has the maximum height. The highest component is different for different
models.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...