SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Note:
•
Unit and decimal place change when the system units change.
•
If there is a fault, the drive will coast to a stop.
•
Set this parameter to 0.0 to disable the function.
•
This function is only active during run when in Auto Mode.
■
Y1-16: Not Maintaining Setpoint Time
No.
(Hex.)
Name
Description
Default
(Range)
Y1-16
(3C0F)
RUN
Not Maintaining Setpoint
Time
Sets the delay time before a Setpoint Not Met condition occurs. The drive must detect the setpoint
difference set in
Y1-15 [Maximum Setpoint Difference]
before the timer will start.
60 s
(0 - 3600 s)
Note:
Set
Y1-15 = 0 [Maximum Setpoint Difference = 0]
to disable this function.
■
Y1-17: Not Maintaining Setpoint Sel
No.
(Hex.)
Name
Description
Default
(Range)
Y1-17
(3C10)
Not Maintaining Setpoint Sel Sets the drive response when the feedback increases to more or decreases to less than the setpoint for
more than the amount set in
Y1-15 [Maximum Setpoint Difference].
0
(0 - 2)
The drive enables the Not Maintaining Set Point detection when:
•
Drive is operating in PID control (
b5-01 ≠ 0 [PID Mode Setting ≠ Disabled
)
•
Drive is operating in AUTO Mode
•
Drive is not in Pre-Charge Mode
•
Drive is not in the sleep state
•
Parameter
Y1-15 > 0 [Maximum Setpoint Difference > 0]
0 : Fault (and Digital Output)
The keypad will show an
NMS [Setpoint Not Met]
fault and the motor coasts to stop. The output terminal set for
H2-
xx = AC [Setpoint Not Maintained]
will activate.
To deactivate the digital output, do a Fault Reset.
•
If Not Maintaining Setpoint condition continues for longer than
Y1-16 [Not Maintaining Setpoint Time]
the drive
will detect an
NMS
fault.
•
If the feedback increases or decreases to less than
Y1-15
from the setpoint before
Y1-16
expires, the drive will
deactivate the output terminal, clear the alarm, and reset
Y1-16
.
1 : Alarm (and Digital Output)
The keypad will show an
NMS [Setpoint Not Met]
alarm and the output terminal set for
H2-xx = AC
will activate.
To deactivate the digital output and clear the alarm, increase or decrease the feedback to less than
Y1-15
from the
setpoint.
Note:
There is no time limit for this condition.
2 : Digital Output Only
The drive will detect Not Maintaining Setpoint and the output terminal set for
H2-xx = AC
will activate.
To deactivate the digital output, increase or decrease the feedback to less than
Y1-15
from the setpoint.
Note:
There is no time limit for this condition.
■
Y1-18: Prime Loss Detection Method
No.
(Hex.)
Name
Description
Default
(Range)
Y1-18
(3C11)
Prime Loss Detection
Method
Sets the units and quantity that the drive will use to determine
LOP [Loss of Prime]
.
0
(0 - 2)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...