Name
Causes
Possible Solutions
oPE34
HAND/OFF/AUTO Input Setting
When
S5-04 = 0 [HAND-OFF-AUTO Behavior =
Legacy]
,
H1-xx = 6D and 6E [MFDI Function
Selection = AUTO Command and HAND Command]
are set at the same time.
Set only one of the two functions
H1-xx = 6D or 6E
.
When
S5-04 = 1 [HAND-OFF-AUTO Behavior =
Normal]
and
b1-02 ≠ 1 [Run Command Selection 1 ≠
Digital Input]
, only one of
H1-xx = 6D or 6E
is set.
Set
H1-xx = 6D and 6E
for operation from terminals, or remove
both input settings.
These parameters are set at the same time:
•
S5-04 = 1
•
b1-02 = 1
•
H1-xx = 6D
Remove the MFDI setting of
H1-xx = 6D
.
Note:
When
S5-04 = 1
and
b1-02 = 1
, the AUTO Mode Run
command comes from the Run command MFDI based on one of
these operation sequence settings:
•
H1-xx = 0 [3-Wire Sequence]
•
H1-xx = 40 [Forward RUN (2-Wire)]
•
H1-xx = 41 [Reverse RUN (2-Wire)]
•
H1-xx = 42 [Run Command (2-Wire Sequence 2)]
Code
Name
Causes
Possible Solutions
oPE36
Bypass Energy Savings Setting Err
These parameters are set at the same time:
•
Z1-16 ≠ 0 [Energy Savings Mode ≠ Disabled]
•
Y4-42 ≠ 0 [Output Disconnect Detection Sel ≠
Disabled]
Set
Z1-16
or
Y4-42
= 0.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...